2023-03-01 12:36:08 | COMMUNITY CENTER |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) SEPARATE PERMIT REQUIRED FOR - EXISTING BUILDING |
| DEMOLITION, FENCES, SITE WALLS, TENNIS COURTS, SHADE |
| STRUCTURES, SITE LIGHTING AND PARKING LOTS. |
| |
| 2) PLEASE PROVIDE THE FOLLOWING STATEMENT ON THE |
| ARCHITECTURAL DRAWINGS - THRESHOLD BLDG. REQUIRED |
| STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE |
| BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| 633 FLORIDA STATUTES. |
| |
| 3) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER |
| THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". |
| YOU CAN E MAIL ME AND ASK FOR A COPY. |
| |
| 4) PLEASE PROVIDE A THRESHOLD INSPECTION PLAN FBC WPB |
| 110.8.1 |
| |
| 5) THE PROVIDED PRODUCT APPROVAL (FL17682-R6) - ON THE |
| FRONT PAGE OF THE PRODUCT APPROVAL UNDER "STATUS" IT |
| SAYS "PENDING FBC APPROVAL" STATUS NEEDS TO SAY |
| "APPROVED". |
| |
| 6) DRAWINGS COV-1, GN-1, DM-1, DM-2, DM-3, PGD-1, |
| PGD-2, PGD-3, UT-1, UT-2, UT-3, DET-1, DET-2, DET-3, |
| HD-1, HD-2, HD-3, HD-4, LT-1, LT-2, LT-3 DO NOT SHOW AS |
| DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| SPECIFIC TYPE OF E-SIGNATURE). |
| |