Plan Review Notes For Permit 23010407 |
Permit Number |
23010407 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-10 15:38:15 | 1) PROVIDE A COMPLETE DESIGN FOR THIS FUESLING STATION | | INCLUDING THE PUMPS AND HOW THEY ARE SECURED TO THE | | TANK. SHOW ANY PIPING THAT WILL BE USED IN TIS DESIGN. | | INCLUDE THE SHUTOFF VALVES THAT APPLY. FMC 1307 | | | | 2) HOW IS THE FUEL INTRODUCED TO THE VEHICLE? IF A | | FLEXIBLE HOSE, SHOW THAT IT IS LISTED AND LABELED IN | | ACCORDANCE WITH UL 536 | | | | 3) WHAT TYPE OF FUEL IS TO BE STORED? | | | | 4) PROVIDE DETAILS FOR THE PUMPS. SHOW THAT THE PUMPS | | ARE LISTED AND LABELED IN ACCORDANCE WITH UL 343. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|