2023-01-20 10:23:22FIRE REVIEW COMMENTS:
  
 (1) DEFINE THE TYPE AND CLASSIFICATION OF THE LIQUIDS
 TO BE STORED IN EACH TANK TO ALLOW FIRE REVIEW TO APPLY
 APPLICABLE CODE REQUIREMENTS. NFPA 30, 4.3
  
 (2) ONCE THE CLASSIFICATION IS PROVIDED, THE APPLICABLE
 CODE SECTIONS ON DISTANCE TO BUILDINGS, VENTING,
 PIPING, DISPENSERS, SIGNAGE, ETC. WILL BE REQUIRED FOR
 THOROUGH CODE REVIEW. NFPA 1, 1.14
  