2023-02-01 13:08:32 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE THE CONNECTED LOAD AND THE PANEL SCHEDULE | | FOR EXISTING PANEL 'C" 60A MCB. NEC NEC 215.2, 220, | | 408.4(A). | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|