Plan Review Notes For Permit 23010360 |
Permit Number |
23010360 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-07 14:17:03 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. REVIEW LOAD CALCULATION (AC/HEAT @ 65%) TO BE IN | | ACCORDANCE WITH 220.82 | | 2. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | SPACE IS MORE THAN 6FT FROM A RECEPTACLE OUTLET. NEC | | 210.52 | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|