Plan Review Notes
Plan Review Notes For Permit 23010315
Permit Number 23010315
Review Stop G
Sequence Number 1
Notes
Date Text
2023-02-02 11:12:531ST REVIEW FBC-2020 RES. GAS
 REVISIONS TO PERMIT- 23010312 & 23010315
 2/2/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS G-1, M-1, & M-2: THE MAKEUP AIR DUCT FOR THE
 RANGE EXHAUST SHALL NOT BE USED TO PROVIDE COMBUSTION
 AIR FOR THE NEW RANGE IN THE ACCESSORY STRUCTURE-
 G2407.1 FBC RES. EXCEPTION 1 UNDER G2407.1 APPLIES ONLY
 TO DRYERS. IF THE INTENTION IS TO PROVIDE A DUCT TO
 SUPPLY THE ADDITIONAL COMBUSTION AIR FOR THE RANGE NOT
 PROVIDED BY THE INDOOR AIR VOLUME, PLEASE REFER TO
 G2407.7 AND SHOW COMPLIANCE WITH G2407.7- G2407.7.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  