Plan Review Notes
Plan Review Notes For Permit 23010129
Permit Number 23010129
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-09 06:45:021ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3108.1 - DOWNSTAIRS BATHROOM -- THE
 KITCHEN AND UPSTAIRS DRAINAGE STACK ARE SHOWN PASSING
 THROUGH THE WET VENT SYSTEM THAT SERVES THE DOWNSTAIRS
 BATHROOM GROUP FIXTURES. ONLY BATHROOM GROUP FIXTURES
 CAN BE INCLUDED WITHIN THE WET VENT. THE KITCHEN AND
 DRAINAGE STACK FROM UPSTAIRS NEEDS TO DISCHARGE
 DOWNSTREAM OF THE WET VENT SYSTEM.
  
 2. 2020 FRC P3108.2.1 - THE VENT CONNECTION FOR THE
 LAVATORY DOWNSTAIRS CANNOT CONNECT BACK TO THE DRAINAGE
 STACK. THE VENT CONNECTION MUST BE AN INDIVIDUAL VENT
 OR COMMON VENT AND WOULD NEED TO GO UP ABOVE THE FLOOD
 RIM OF THE UPSTAIRS BATHROOMS BEFORE CONNECTING TO THE
 UPSTAIRS VENT BRANCHES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  