2023-01-09 06:45:02 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FRC P3108.1 - DOWNSTAIRS BATHROOM -- THE |
| KITCHEN AND UPSTAIRS DRAINAGE STACK ARE SHOWN PASSING |
| THROUGH THE WET VENT SYSTEM THAT SERVES THE DOWNSTAIRS |
| BATHROOM GROUP FIXTURES. ONLY BATHROOM GROUP FIXTURES |
| CAN BE INCLUDED WITHIN THE WET VENT. THE KITCHEN AND |
| DRAINAGE STACK FROM UPSTAIRS NEEDS TO DISCHARGE |
| DOWNSTREAM OF THE WET VENT SYSTEM. |
| |
| 2. 2020 FRC P3108.2.1 - THE VENT CONNECTION FOR THE |
| LAVATORY DOWNSTAIRS CANNOT CONNECT BACK TO THE DRAINAGE |
| STACK. THE VENT CONNECTION MUST BE AN INDIVIDUAL VENT |
| OR COMMON VENT AND WOULD NEED TO GO UP ABOVE THE FLOOD |
| RIM OF THE UPSTAIRS BATHROOMS BEFORE CONNECTING TO THE |
| UPSTAIRS VENT BRANCHES. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |