2023-01-17 12:44:09 | |
| 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 23010098 |
| 1/17/23 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A-1.1: THE PLAN SHOWS A GRILL IN THE PERGOLA |
| WHICH IS ASSUMED TO BE A GAS GRILL. PLEASE CLARIFY IF |
| THE GRILL WILL BE FIRED USING A PORTABLE LP TANK OR |
| CONNECTED TO THE EXISTING GAS PIPING SYSTEM- SEC. |
| 107.2.1 WPB. PLEASE NOTE IF CONNECTING TO THE EXISTING |
| GAS SERVICE A COMPLETE RISER DRAWING WILL BE REQUIRED |
| THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND |
| APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & G2412.4 |
| FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE |
| RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) A-1.1: THE SPECS FOR THE GRILL MANUFACTURER PROVIDES |
| INSTALLATION CLEARANCES AND LIMITATIONS WHICH MAY |
| PROHIBIT THE INSTALLATION UNDER COMBUSTIBLE |
| CONSTRUCTION. PLEASE REVIEW THE SPECS AND SUBMIT ONLY |
| THE PAGES THAT DETAIL THE REQUIRED CLEARANCES. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |