2023-03-22 18:55:18 | RESIDENTIAL(R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23010083 |
| 230 ARGYLE RD (MAIN HOUSE ADDITION/ALTERATION) |
| |
| NOTE: |
| ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- BEDROOM EGRESS WINDOWS: |
| A)EGRESS WINDOW #12 (24"X36" CASEMENT) FOR BEDROOM #2 |
| DOESN'T COMPLY WITH EGRESS SEC. R310.2.1 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| B)EGRESS WINDOW #16 (50"X56" S.H.) FOR BEDROOM #3 |
| DOESN'T COMPLY WITH EGRESS SEC. R310.2.1 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| C)EGRESS WINDOW #14 (32"X53" CASEMENT) FOR MASTER |
| BEDROOM DOESN'T SEEM TO COMPLY WITH THE MINIMUM CLEAR |
| WIDTH OPENING REQUIREMENTS OF SEC. R310.2.1 |
| FBC-RESIDENTIAL BECAUSE OF THE HINGE OPERATION. PROVIDE |
| MANUFACTURER'S SPECIFICATIONS SHOWING COMPLIANCE ALL |
| THE EGRESS REQUIREMENTS, INCLUDING THE MIN. CLEAR |
| WIDTH. |
| |
| 2- PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE |
| DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT |
| WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES. |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. |
| 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| 3- PROJECT LOCATION SHOWN ON SHEET 2 IS INCORRECT. |
| REVISE MAP VIEW AND AERIAL VIEW. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| NOTE: ARCHITECT TO SHOW NORTH ARROW ON EACH FLOOR PLAN |
| TO AVOID CONFLICTS/DELAYS. |
| |
| 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE PROPOSED ELEVATOR SHAFT AND |
| ELEVATOR CAB SHOWING COMPLIANCE WITH SEC. R301.1 |
| FBC-RESIDENTIAL AND SEC. R321 FBC-RESIDENTIAL |
| RESPECTIVELY. |
| NOTE: PROVIDE COMPLETE INFORMATION NOW OR THIS MAY BE |
| SUBMITTED UNDER A SEPARATE PERMIT. IF SEPARATE PERMIT |
| IS PREFERRED, THEN SPECIFY ON PLANS. |
| |
| 5- LANDING IS REQUIRED ON THE EXTERIOR SIDE OF DOOR |
| LEADING TO THE PORT COCHERE AREA. |
| SEC. R311.3.2 FBC-RESIDENTIAL. |
| |
| 6- STAIR DETAIL ON SHEET 19: |
| A)PROVIDE COMPLETE FRAMING DETAILS FOR STAIRWAY |
| MATCHING PROPOSED ONE. SPECIFY FRAMING MEMBERS AND |
| CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL. SEC. R311.7 |
| FBC-RESIDENTIAL. |
| |
| B)PROVIDE HANDRAIL DETAIL SHOWING COMPLIANCE WITH SEC. |
| R311.7.8 FBC-RESIDENTIAL. |
| NOTE: SHOW 2"X6" RAIL DETAIL SHOWING COMPLIANCE WITH |
| SEC. R311.7.8.3 FBC-RESIDENTIAL. |
| |
| C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11 |
| FBC-RESIDENTIAL. NEED FIREBLOCKING AT TOP AND BOTTOM OF |
| THE STAIRS. |
| |
| D)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR STAIR |
| NOSING AS REQUIRED BY SEC. R311.7.5.3 FBC-RESIDENTIAL. |
| NOTE: STAIR DETAIL SPECIFIES 2"X0" TREAD INCLUDING 1" |
| NOSE. SIZE OF TREAD IS NOT CLEAR AND THE MIN. TREAD |
| SIZE IS 10" AND THE NOSING IS ADDITIONAL. |
| |
| 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| DRAFSTOPPING IN SECOND FLOOR AREAS AS REQUIRED BY SEC. |
| R302.12 FBC-RESIDENTIAL. |
| |
| 8- PROVIDE ROOF SHEATHING NAILING SPECIFICATIONS |
| SHOWING COMPLIANCE WITH NEW 2020 FBC-RESIDENTIAL |
| SPECIFICATIONS. SPECIFY NAIL TYPE, SIZE AND SPACING. |
| COORDINATE ROOF SHEATHING SPECIFICATIONS ON SHEET 17, |
| 19 AND 23 TO MATCH. |
| NOTE: NEED TO USE RING SHANK NAILS. ROOF SHEATHING |
| NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE FIELD AND |
| EDGES AS REQUIRED BY SEC. R803.2.3.1 AND TABLE |
| R803.2.3.1 FBC-RESIDENTIAL. |
| |
| 9- WOOD FRAMED WALLS AND STUCCO: NEED TO SPECIFY 2 |
| LAYERS OF WATER RESISTIVE BARRIERS AS REQUIRED BY SEC. |
| R703.7.3 WATER-RESISTIVE BARRIERS. |
| |
| 10-SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE |
| BEDROOMS (NEW AND EXISTING)AS REQUIRED BY SEC. R315.1 |
| FBC-RESIDENTIAL. |
| |
| 11- FOUNDATION PLAN: |
| A)NEED TO SPECIFY VAPOR BARRIER FOR THE CONCRETE SLAB |
| AS REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL. |
| |
| B)PROPOSED FOUNDATION IS BLOCKING EXISTING CRAWL SPACE |
| VENTS. PROVIDE COMPLETE FOUNDATION PLAN SHOWING |
| LOCATION AND SIZE OF VENTILATION OPENINGS SHOWING |
| COMPLETE COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. |
| R408 FBC-RESIDENTIAL. |
| |
| 12- FOUNDATION PLAN AND SECOND FLOOR FRAMING PLANS: |
| THERE ARE SOME STRUCTURAL CONNECTORS THAT ARE NOT |
| SPECIFIED FOR SOME COLUMNS AND BEAMS. SPECIFY |
| CONNECTIONS AT TOP AND BOTTOM OF ALL COLUMNS. SPECIFY |
| CONNECTORS AT EACH END OF ALL NEW BEAMS. ALSO, SPECIFY |
| BEAM SIZE AND CONNECTORS FOR BEAM BETWEEN KITCHEN AND |
| BREAKFAST AREA. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 14- FLAT ROOFS: ROOF SCUPPERS: SPECIFY SIZE OF NEW |
| SCUPPERS AND PROVIDE COMPLETE INFORMATION OF OVERFLOW |
| SCUPPERS (LOCATION AND SIZE) AS REQUIRED BY SEC. |
| R903.4.1 FBC-RESIDENTIAL. |
| |
| 15- DOORS AND WINDOWS STRUCTURAL BUCK: PROVIDE |
| STRUCTURAL BUCK DETAIL SHOWING COMPLIANCE WITH SEC. |
| R609.7.2.1 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK |
| SIZE AND FASTENING. |
| NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| FBC-RESIDENTIAL. |
| |
| 16- ENERGY CALCULATIONS: |
| A)SEPARATE ENERGY CALCULATIONS IS REQUIRED FOR EACH |
| BUILDING. MAIN HOUSE AND GARAGE/APT STRUCTURE. SEC. |
| R101.3 FBC-ENERGY CONSERVATION. |
| NOTE: ENERGY CALCULATIONS WILL BE REVIEWED ONCE THEY |
| ARE SUBMITTED FOR EACH BUILDING TO VERIFY BUILDING |
| SPECIFIC INFORMATION. |
| |
| B)SUBMIT ENERGY CALCULATIONS AND A/C EQUIPMENT LOAD |
| CALCULATIONS ON SEPARATE PDF FILES. THIS WILL HELP |
| EXPEDITE THE REVIEW PROCESS AND WILL HELP TO AVOID |
| CONFLICTS/DELAYS IF ENERGY CALCULATIONS ARE APPROVED |
| AND EQUIPMENT SIZING CALCULATIONS ARE NOT OR VICE VERSA |
| SINCE A/C CALCULATIONS ARE DONE UNDER A SEPARATE |
| MECHANICAL REVIEW. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND |
| JURISDICTION NUMBER (THIS JURISDICTION IS 604700). |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D)COORDINATE THERMAL ENVELOPE INSULATION WITH THERMAL |
| ENVELOPE INFORMATION REVISION REQUIRED ON ITEM #13 |
| ABOVE. |
| |
| E)ROOF TYPE AND MATERIAL TO MATCH PLANS FOR EACH |
| BUILDING. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)REVISE DOORS INFORMATION. IT LOOKS LIKE THE |
| INFORMATION SUBMITTED IS FOR THE OVERHEAD GARAGE DOOR. |
| DOORS INFORMATION IS FOR THE DOORS SEPARATING A/C AREAS |
| FROM NON-A/C AREAS. NOT FROM GARAGE TO OUTSIDE. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| G)REVISE WINDOWS INFORMATION TO MATCH PLANS. REVISE |
| WINDOWS ORIENTATION, AREA AND OVERHANG DEPTH AND |
| SEPARATION TO MATCH PLANS. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 17-PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR |
| LATER AS A DEFERRED SUBMITTAL). |
| |
| A)FLAT ROOF: SELECTED ASSEMBLY W-1 ON PAGE 6 OF 93 |
| DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. |
| THEREFORE, IT CANNOT BE USED FOR BONDED INSULATION AND |
| ROOF COVER ASSEMBLIES. NEED TO SPECIFY ANOTHER |
| ASSEMBLY. IF THE SELECTED ASSEMBLY DOESN'T MEET THE |
| DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND |
| SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| NOTE: PLANS DON'T SPECIFY INSULATED ROOF ASSEMBLY. |
| COORDINATE WITH ARCHITECT. |
| |
| B)ROOF TILE FLORIDA PRODUCT APPROVAL FL7849-R16: |
| CLEARLY IDENTIFY ADHESIVE PADDY SIZE TO BE USED AS |
| REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO |
| VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| R301.2.1 FBC-RESIDENTIAL. |
| NOTE: COORDINATE WITH FOAM ADHESIVE COMMENT BELOW. |
| CLARIFY WHY SUBMITTING TWO ROOF TILE PRODUCT APPROVALS |
| WITH DIFFERENT TILE SPECS. |
| BARCELONA 900 AND ESTATE "S". WHICH ONE IS GOING TO BE |
| INSTALLED? |
| |
| C)ROOF TILE ADHESIVE FLORIDA PRODUCT APPROVAL FL6332-R9 |
| SUBMITTED: CLEARLY IDENTIFY ADHESIVE PADDY SIZE TO BE |
| USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| R301.2.1 FBC-RESIDENTIAL. |
| NOTE: COORDINATE WITH ROOF TILE COMMENT ABOVE. |
| |
| D)POLYGLASS ROOF TILE UNDERLAYMENT PRODUCT APPROVAL FL |
| 1654-R9 SUBMITTED: CLEARLY MARK WHICH UNDERLAYMENT IS |
| GOING TO BE INSTALLED AND CLEARLY IDENTIFY ATTACHMENT. |
| SEE SEC. 5.8 AND SEC. 5.8.3 OF PRODUCT APPROVAL |
| SUBMITTED. SPECIFY WHICH ASSEMBLY FROM SEC. 5.8.3 IS |
| GOING TO BE INSTALLED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: THERE ARE SEVERAL ROOF UNDERLAYMENTS SUBMITTED. |
| CLARIFY WHICH ONE IS GOING TO BE USED TO AVOID |
| CONFLICTS/DELAYS. |
| |
| E)OWES CORNING ROOF TILE UNDERLAYMENT PRODUCT APPROVAL |
| FL9776-R16 SUBMITTED: CLEARLY MARK WHICH UNDERLAYMENT |
| IS GOING TO BE INSTALLED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| F)OWES CORNING ROOF TILE UNDERLAYMENT FL1602-R13. |
| CLEARLY SPECIFY WHICH UNDERLAYMENT IS GOING TO BE |
| INSTALLED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| G)ENTRY DOOR NOA 21-0510.09 SUBMITTED DOESN'T MEET THE |
| CALCULATED DESIGN PRESSURES SHOWN ON SHEET 2. NEED DOOR |
| THAT MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES. |
| SEC R301.2.1 FBC-RESIDENTIAL. |
| |
| H)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| FOR ALL HORIZONTAL AND VERTICAL MULLIONS TO BE |
| INSTALLED TO VERIFY PRESSURES. SEC. R301.2.1 |
| FBC-RESIDENTIAL). |
| NOTE: SEE WINDOW #9 (90"X24"). VERIFY SIZE OF MULLION |
| AND DESIGN PRESSURES. |
| |
| I)NEED PRODUCT APPROVAL FOR ARCHED WINDOWS. SEE PLANS |
| FOR SIZES. |
| |
| 18-DESIGNER OF RECORD TO REVIEW PRODUCT APPROVALS THAT |
| ARE NEW OR REVISED. SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |