2023-01-13 15:31:20ELECTRIC REVIEW FAILED
 1) PROVIDE PANEL SCHEDULE AND LOAD CALCULATION FOR
 UPSTREAM ELECTRIC PANEL. PROVIDE A NEUTRAL CALCULATION
 IF REDUCED SIZE CONDUCTOR IS USED. NEC 215.5
 2) CORRECT #4 CU CONDUCTOR SIZE TO NEW 100 AMP ELECTRIC
 SUB PANEL TO COMPLY WITH NEC 310.15. #4 CU CONDUCTOR
 RATED AT 85 AMPS, NEXT SIZE STANDARD BREAKER IS 90 AMP.
 NEC 310.15 AND NEC 240.6
 3) PROVIDE FLOOR PLAN DETAILING ALL ELECTRICAL EQIPMENT
 LOCATIONS. FBC 107.2
 4) INCLUDE ON ALL CONTRACTOR PREPARED DRAWINGS THE
 NAME, LICENSE NUMBER AND SIGNATURE OF THE CONTRACTOR .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  