2023-01-13 15:31:20 | ELECTRIC REVIEW FAILED | | 1) PROVIDE PANEL SCHEDULE AND LOAD CALCULATION FOR | | UPSTREAM ELECTRIC PANEL. PROVIDE A NEUTRAL CALCULATION | | IF REDUCED SIZE CONDUCTOR IS USED. NEC 215.5 | | 2) CORRECT #4 CU CONDUCTOR SIZE TO NEW 100 AMP ELECTRIC | | SUB PANEL TO COMPLY WITH NEC 310.15. #4 CU CONDUCTOR | | RATED AT 85 AMPS, NEXT SIZE STANDARD BREAKER IS 90 AMP. | | NEC 310.15 AND NEC 240.6 | | 3) PROVIDE FLOOR PLAN DETAILING ALL ELECTRICAL EQIPMENT | | LOCATIONS. FBC 107.2 | | 4) INCLUDE ON ALL CONTRACTOR PREPARED DRAWINGS THE | | NAME, LICENSE NUMBER AND SIGNATURE OF THE CONTRACTOR . | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | |
|