2023-01-13 10:14:06 | 1ST REVIEW FMC | | PERMIT: 23010048 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET 1 OF 5: UNDER THE AIR BALANCE REPORT; A NOTE | | STATES ??? BUILDING HVAC SYSTEM TO PROVIDE MORE THAN | | 600 CFM TO INSURE OVERALL BUILDING BALANCE IS POSITIVE. | | PROVIDE THE BUILDING MECHANICAL SYSTEM CALCULATIONS | | SHOWING THAT THE SYSTEM CAN PRODUCE THE REQUIRED | | ADDITIONAL AIR FOR THIS HOOD SYSTEM. FBC 107.3.5 | | | | 2) SHEET 2 OF 5: EXPLAIN THE USE OF THE 2 - 5 TON | | CONDENSING UNITS. | | | | 3) PROVIDE A DEMO DRAWING OF WHAT IS TO BE REMOVED. | | FBC 107.3.5 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|