Plan Review Notes For Permit 23010047 |
Permit Number |
23010047 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-03-01 12:01:30 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5; | | EXPOSURE (D); ENCLOSURE (OPEN); ROOF HEIGHT (H<15); | | ULTIMATE WIND SPEED (170) IS NOT CORRECT. THE CORRECT | | ENCLOSURE FOR THE LISTED ADDRESS IS ENCLOSED; THIS IS | | AN ENCLOSED STRUCTURE. PRODUCT APPROVAL FL16709-R10 | | WILL NOT SATISFY EXPOSURE CATEGORY D ENCLOSED AREAS | | WITHOUT USING INSULATION OR PROVIDING ENGINEERED. | | SECOND REQUEST. | | | | ENHANCED NAILING. PLEASE NOTE THAT SUBMITTAL OF | | ADDITIONAL AND/OR REVISED MATERIALS MAY RESULT IN NEW | | PLAN REVIEW COMMENTS. | | |
|