Plan Review Notes For Permit 22121414 |
Permit Number |
22121414 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-04 08:40:11 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. REVIEW AND UPDATE THE LOAD CALCULATION FOR SERVICE, | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | SERVICE IS ADEQUATE. | | NEC 215.2, 220, | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|