Plan Review Notes
Plan Review Notes For Permit 22121242
Permit Number 22121242
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-12-28 13:59:50THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 PROVIDE NON-COMBUSTIBLE CANOPY MATERIAL.
 PER FL STATUTE 633.202
  
 A TENT UP TO 900 SQUARE FEET IS EXEMPT FROM THE FLORIDA
 FIRE PREVENTION CODE, INCLUDING THE NATIONAL CODES
 INCORPORATED BY REFERENCE.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]