2022-12-28 13:59:50 | THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L |
| FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| COMMENTS: |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES |
| SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET |
| AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| ENCLOSURE. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| |
| TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| BUILDING STRUCTURES. |
| |
| TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| |
| POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| LOCATIONS. |
| |
| PROVIDE NON-COMBUSTIBLE CANOPY MATERIAL. |
| PER FL STATUTE 633.202 |
| |
| A TENT UP TO 900 SQUARE FEET IS EXEMPT FROM THE FLORIDA |
| FIRE PREVENTION CODE, INCLUDING THE NATIONAL CODES |
| INCORPORATED BY REFERENCE. |
| |