Plan Review Notes For Permit 22121144 |
Permit Number |
22121144 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-07-20 15:46:03 | RE LOCATING A SFR - NEW FOUNDATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE A SOIL REPORT. | | | | 2) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE | | BUILDING, THE BASE FLOOD DELINEATION LINES AND THE FEMA | | BASE FLOOD ELEVATIONS. | | | | 3) CRAWL SPACE = ADDED AIR VENTS WILL NOT WORK FOR | | FLOOD VENTS UNLESS THE LOUVER OPENINGS ARE 3" APART - | | R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. | | (2.2.) OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM) | | IN ANY DIRECTION IN THE PLANE OF THE WALL. R408.7 FLOOD | | RESISTANCE. | | FOR BUILDINGS LOCATED IN FLOOD HAZARD AREAS AS | | ESTABLISHED IN TABLE R301.2(1): | | | | A).WALLS ENCLOSING THE UNDER-FLOOR SPACE SHALL BE | | PROVIDED WITH FLOOD OPENINGS IN ACCORDANCE WITH SECTION | | R322.2.2. | | | | B).THE FINISHED GROUND LEVEL OF THE UNDER-FLOOR SPACE | | SHALL BE EQUAL TO OR HIGHER THAN THE OUTSIDE FINISHED | | GROUND LEVEL ON AT LEAST ONE SIDE. | | | | | | 4) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | FBC WPB 107.3.5 | | | | 5) PLEASE PROVIDE FLOOD VENT CERTIFICATION/EVALUATION | | AND PRODUCT APPROVALS. | | | | 6) THE TOILET ROOM IN THE GARAGE WILL NEED FLOOD VENTS | | - FBC R322.2.2 | | | | |
|