2023-02-03 15:10:05 | RE LOCATING A SFR - NEW FOUNDATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) DRAWING S-1 - SECTION 1/S-1 - PLEASE SHOW THE |
| BUILDING ANCHORAGE (HURRICANE STRAPS) TO THE NEW |
| FOUNDATION - FBC R301.1 |
| |
| 2) DRAWING S-1 -SECTIONS 2 AND 3 LOOK TO BE IN THE |
| WRONG PLACE ON THE PLAN - PLEASE CHECK CUT SECTION |
| LOCATIONS. |
| |
| 3) DRAWING S-4 - SECTIONS 6 AND 7 - LOCATIONS ARE NOT |
| SHOWN ON THE PLAN. |
| |
| 4) DRAWING S-1 - SECTIONS 4 AND 5 - LOCATIONS ARE NOT |
| SHOWN ON THE PLAN. |
| |
| 5) DRAWING A-4 - PLEASE SHOW THE STEP DIMENSION FROM |
| THE FIRST FLOOR TO THE FRONT PORCH. |
| |
| 6) PLEASE SHOW UNDER FLOOR VENTILATION LOCATIONS PER - |
| FBC R408.1 VENTILATION. |
| THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR |
| JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE |
| OCCUPIED BY A BASEMENT) SHALL HAVE VENTILATION OPENINGS |
| THROUGH FOUNDATION WALLS OR EXTERIOR WALLS. THE MINIMUM |
| NET AREA OF VENTILATION OPENINGS SHALL BE NOT LESS THAN |
| 1 SQUARE FOOT (0.0929 M2) FOR EACH 150 SQUARE FEET (14 |
| M2) OF UNDER-FLOOR SPACE AREA, UNLESS THE GROUND |
| SURFACE IS COVERED BY A CLASS 1 VAPOR RETARDER |
| MATERIAL. WHERE A CLASS 1 VAPOR RETARDER MATERIAL IS |
| USED, THE MINIMUM NET AREA OF VENTILATION OPENINGS |
| SHALL BE NOT LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR |
| EACH 1,500 SQUARE FEET (140 M2) OF UNDER-FLOOR SPACE |
| AREA. ONE SUCH VENTILATING OPENING SHALL BE WITHIN 3 |
| FEET (914 MM) OF EACH CORNER OF THE BUILDING. |
| |
| 7) SHOW THE ACCESS FOR THE CRAWL SPACE - FBC R408.4 |
| ACCESS. |
| ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR SPACES. |
| ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF |
| 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS |
| THROUGH A PERIMETER WALL SHALL BE NOT LESS THAN 16 |
| INCHES BY 24 INCHES (407 MM BY 610 MM). WHERE ANY |
| PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, AN |
| AREAWAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM BY |
| 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY |
| SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING. |
| THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER |
| A DOOR TO THE RESIDENCE. |
| |
| 8) PLEASE PROVIDE A SOIL REPORT. |
| |
| 9) PLEASE SHOW THE STORM WATER DRAINAGE FLOW AWAY FROM |
| THE BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE |
| SITE PLAN - FBC WPB107.2.5 SITE PLAN. THE CONSTRUCTION |
| DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT |
| SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE |
| THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| WATER RETAINING SWALES) |
| |
| 10) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE |
| BUILDING, THE BASE FLOOD DELINEATION LINES AND THE FEMA |
| BASE FLOOD ELEVATIONS. |
| |
| 11) PLEASE SHOW THE GARAGE FLOOR ELEVATION - ELEVATIONS |
| LOWER THAN 2 FEET ABOVE FEMA BASE FLOOD ELEVATION WILL |
| REQUIRE FLOOD VENTS - FBC R322.2.2 |
| |
| 12) PLEASE SHOW THE FLOOR ELEVATION FOR THE |
| LAUNDRY/RESTROOM IN THE GARAGE - MUST BE 2 FEET ABOVE |
| FEMA BASE FLOOD ELEVATION FBC R322.2.1 |
| |
| 13) PLEASE SHOW THE GARAGE FLOOR TO SLOPE PER FBC |
| R309.1 |
| |
| 14) R408.7 FLOOD RESISTANCE. |
| FOR BUILDINGS LOCATED IN FLOOD HAZARD AREAS AS |
| ESTABLISHED IN TABLE R301.2(1): |
| |
| 1.WALLS ENCLOSING THE UNDER-FLOOR SPACE SHALL BE |
| PROVIDED WITH FLOOD OPENINGS IN ACCORDANCE WITH SECTION |
| R322.2.2. |
| |
| 2.THE FINISHED GROUND LEVEL OF THE UNDER-FLOOR SPACE |
| SHALL BE EQUAL TO OR HIGHER THAN THE OUTSIDE FINISHED |
| GROUND LEVEL ON AT LEAST ONE SIDE. |
| |
| 15) PLEASE SHOW THE REQUIRED TERMITE PROTECTION - FBC |
| R318 |
| |
| 16) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - |
| FBC WPB 107.3.5 |
| |
| 17) PLEASE PROVIDE FLOOD VENT CERTIFICATION/EVALUATION |
| AND PRODUCT APPROVALS. |
| |
| 18) A SEPARATE PERMIT IS REQUIRED FOR - EXISTING |
| BUILDING DEMO AND DRIVEWAY. |