2023-04-04 16:35:44PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. SUBMIT GENERATOR PAD DRAWINGS WITH
 GENERATOR TO PAD ANCHORING DETAILS. IF A PREFABRICATED
 GENERATOR PAD WILL BE USED, SUBMIT SIGNED AND SEALED
 SITE SPECIFIC ENGINEERING FOR IT. FBC AMENDMENTS
 107.2.1
  
 2) NOT RESOLVED. THE GENERATOR IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA. THE GENERATOR IS REQUIRED TO BE AT
 OR ABOVE THE FINISH FLOOR ELEVATION OF THE HABITABLE
 SPACE OF THE DWELLING OR THE BFE PLUS 2 FEET. THE BFE
 IS 6 FT NAVD AT THE GENERATOR'S PROPOSED LOCATION.
  
 3) NOT RESOLVED. THE GENERATOR EXHAUST IS REQUIRED TO
 BE AT LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING.
 R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.