2023-02-15 09:05:20 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD | | ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD | | WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC | | ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1 | | | | 2) THE GENERATOR IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA. THE GENERATOR IS REQUIRED TO BE AT OR ABOVE THE | | FINISH FLOOR ELEVATION OF THE HABITABLE SPACE OF THE | | DWELLING OR THE BFE PLUS 2 FEET. THE BFE IS 6 FT NAVD | | AT THE GENERATOR'S PROPOSED LOCATION. | | | | 3) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|