2023-01-13 13:26:44ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE A SIMPLE DRAWING INDICATING WIRING TO
 BE DONE. KEEP IN MIND THAT THE WATER HEATER WILL NEED
 TO BE HARDWIRED TO BE COMPLIANT
 WITH NEC 400,12 (1). PLEASE HAVE THE ELECTRICAL
 CONTRACTOR PLACE HIS NAME AND LICENSE NUMBER AND
 SIGNATURE ON ANY DRAWINGS THEY PREPARE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  