2022-12-30 11:35:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF PROPSED WOOD FLOOR OVER |
| EXISTING TILE, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR |
| THE ACTUAL PROPOSED WOOD FLOORING. |
| |
| WOOD FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT |
| ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR WOOD LVT, AND |
| WOOD/VINYL LAMINATES. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE WOOD |
| FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| THE FIRE BEHAVIOR RATING. |
| |
| |
| |
| 2) THERE IS AN INDICATION OF A NEW SHOWER THAT MAY |
| INCLUDE DEMO/DAMAGE TO AN EXISTING RATED FIRE WALL. |
| |
| ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED, |
| ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEGMENT ON THE FLOOR |
| PLAN IN THAT AREA. |
| |
| |
| |
| 3) IS THE WOOD FLOORING GOING EXTEND ONTO THE BALCONY? |
| |
| FOR THE OFFICIAL RECORD, PLEASE INDICATE THE PROPOSED |
| LOCATIONS OF FLOORING ON THE FLOOR PLAN. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |