2023-01-24 17:09:14PLEASE ADDRESS THE ORIGINAL 1ST CYCLE REVIEW COMMENT.
 FMC 403.3.1.1 TELLS US TO PROVIDE THE REQUIRED OUTDOOR
 AIR TO EACH OCCUPANCY CLASSIFICATION IN THIS TENANT
 SPACE. IT APPEARS THAT THE DESIGNER HAS USED 5 AS THE
 OCCUPANT DENSITY FOR EACH SPACE. THE RECEPTION AREA
 SHOULD USE 30 AND THE CONFERENCE ROOMS SHOULD USE 50.
  
 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH
 USE OF SPACE IN THIS TENANT I.E. OPEN OFFICES, OFFICES,
 CORRIDORS, CONFERENCE ROOMS, RECEPTION AREA. FMC
 403.3.1.1 AND TABLE 403.3.1.1
  