Plan Review Notes
Plan Review Notes For Permit 22121061
Permit Number 22121061
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-31 12:23:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22121061
 ADD: 1401 FORUM WAY # 600
 CONT: HALLMARK CONSTRUCTION
 TEL: 561-324-8556
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 31ST/ 2023
 ACTION: DENIED
  
 1) THE FLOOR PLAN A1.1 NOTE # 8 REFERS TO A NEW HI-LOW
 DRINKING FOUNTAIN REFERS TO SHEET A0.2 FOR MOUNTING
 DETAILS. SHEET A0.2 DOES NOT SHOW A HI-LOW DRINKING
 FOUNTAIN A LOW DRINKING FOUNTAIN AND A BOTTLE FILL
 STATION PLEASE PROVIDE COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTION 602.7 SPOUT HEIGHT FOR
 THE STANDING PERSONS SHALL BE BETWEEN 38 TO 43 INCHES
 ABOVE FINISH FLOOR.
  
 2) SHEET A1.1 THE RESTROOMS 621 & 622 BOTH SHOW A
 INSWING DOOR WHAT IS MISSING IS THE REQUIRED 30X48 INCH
 CLEAR FLOOR SPACE BEYOND THE ARC OF THE DOOR. USUALLY
 AT A 45% ANGLE TO THE DOOR ENTRANCE. SEE FIGURE
 604.8.1.6 EXCEPTION # 2.
  
 3) SHEET A1.3 RESTROOMS 623 JANITORS CLOSET, 621 & 622
 ALL SHOW P-1 WALL FINISHES GENERAL WALL PAINT. 2020
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE. 1210.2.2 WALLS & PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  