2023-05-04 11:24:00 | COMMERCIAL ADDITION/REMODEL |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE |
| LISTED ON THE DRAWINGS BY THE PRODUCT APPROVAL NUMBER. |
| THE REVISED DRAWINGS DO NOT SHOW THE PRODUCT APPROVAL |
| NUMBERS FOR THE WINDOWS AND DOORS. FBC 107.3.4 |
| |
| 2) PLEASE SHOW THE SOUTH WALL OF THE BUILDING WHICH IS |
| 7 1/2 FEET FROM THE CENTER OF THE ALLY TO BE 1 HOUR |
| FIRE RATED PER FBC TABLE 602 (THE NOTE FOR THE WALL HAS |
| BEEN REMOVED ON THE REVISED DRAWINGS). |
| |
| 3) PLEASE SHOW THE OUTDOOR SERVING COUNTER TO BE |
| ACCESSIBLE PER FBC A 904.4 OR 902.3 (THE NOTE SAYING |
| STAFF ONLY HAS BEEN REMOVED ON THE REVISED DRAWINGS) |
| (THE FOOT REST IS BACK ON THE REVISED DRAWING). |
| |
| 4) PLEASE PROVIDE DETAILS OR PRODUCT APPROVALS SHOWING |
| ATTACHMENTS ETC. FOR THE EXTERIOR CORRUGATED METAL WALL |
| FINISH - FBC 1609.1 |
| |
| 5) DRAWINGS SP1.2, A2.1, NEED TO BE SIGNED AND SEALED |
| BY THE DESIGNER - SIGNED AND SEALED DRAWINGS IN |
| PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| E-SIGNATURE). |
| |
| |
| |