Plan Review Notes
Plan Review Notes For Permit 22121052
Permit Number 22121052
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-09 16:24:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22121052 2025 N DIXIE HWY
  
 1ST REVIEW
  
 A SEPARATE PERMIT FOR GREASE INTERCEPTOR IS REQUIRED TO
 BE SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT
 (AS APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD"
 (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR
 SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER(S).
  
 PLUMBING COMMENTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
 ***A) PLAN G1.2: PROVIDE ADDITIONAL DETAILS (PLAN AND
 ELEVATION) FOR STANDARD ROLL IN SHOWER WITH SEAT
 SHOWING DIMENSIONS, LOCATIONS AND HEIGHTS OF GRAB BARS,
 CONTROL VALVE, FAUCETS, SHOWER SPRAY UNIT. COMPLY WITH
 FBC ACC 608.2.2, 608.3.2, 608.5.2, 608.6, 609.4, 610.3,
 610.3.1.
 ***B) PROVIDE DETAIL FOR ACCESSIBLE WASHER AND DRYER
 SHOWING COMPLIANCE WITH FBC ACC 611.3
 ***C) PROVIDE CLEAR FLOOR SPACE FOR ACCESSIBLE WASHER
 AND DRYER SHOWING COMPLIANCE WITH FBC ACC 611.2, 305.
  
 2. PER FBC 607.1.1, 613.1, PROVIDE A
 TEMPERATURE-ACTUATED MIXING VALVE, INSTALLED TO REDUCE
 WATER TEMPERATURES TO DEFINED LIMITS, SHALL COMPLY WITH
 ASSE 1017. SUCH VALVE SHALL BE INSTALLED AT THE HOT
 WATER SOURCE. THIS PROTECTION LEVEL IS IN ADDITION TO
 THE REQUIREMENTS NEEDED FOR PUBLIC HAND WASHING
 DICTATED BY FBC PL 419.5, 607.1.2.
  
 3. IT APPEARS THE HOT WATER PIPING FROM THE HOT WATER
 SOURCE TO THE PUBLIC LAVATORIES EXCEEDS 2 FEET. REFER
 TO TABLE C404.5.1 FBC EC- THE 1/2 -INCH HOT WATER PIPE
 TO THE LAVATORY SHALL NOT EXCEED 2 FEET FROM THE HOT
 WATER SOURCE.
  
 4. RE: P-2.1, P-5.1; CIRCUIT VENTED BRANCH FOR WATER
 CLOSETS
 ***A) THE CIRCUIT VENT CONNECTION SHALL BE LOCATED
 BETWEEN THE TWO MOST UPSTREAM FIXTURE DRAINS (WATER
 CLOSETS). FBC PL 914.2
 ***B) FIXTURES OTHER THAN THE CIRCUIT VENTED FIXTURES
 DISCHARGING TO THE CIRCUIT VENTED BRANCH SHALL BE
 INDIVIDUALLY OR COMMON VENTED. FBC PL 914.5
  
 5. RE: P-2.1, P-5.1; SHOWER DRAINS
 ***A) BRANCH SHALL BE SIZED 3 INCH TO THE CONNECTION
 WITH MOST UPSTREAM SHOWER FIXTURE DRAIN. FBC PL TABLE
 915.2.2
 ***B) VENT SHALL CONNECT ABOVE THE CENTERLINE OF THE
 DRAIN OF THE HORIZONTAL DRAIN AND SHALL RISE VERTICALLY
 TO A POINT NOT LESS THAN 6 INCHES ABOVE THE FLOOD LEVEL
 RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED
 PER FBC PL 905.3 AND 905.4. O BE CLEAR, THERE SHALL BE
 NO HORIZONTAL TRAVEL BETWEEN THE BRANCH AND THE
 VERTICAL PORTION OF THE VENT.
 ***C) PER FBC PL 915.2.5, SHOWER FIXTURE DRAINS SHALL
 NOT EXCEED THE MAXIMUM ALLOWABLE DISTANCE FROM TRAP TO
 VENT AS ALLOWED IN FBC PL TABLE 909.1 UNLESS SIZED THE
 SAME AS THE BRANCH.
  
 6. TRAPPED FLOOR SINK DISCHARGING TO GREASE INTERCEPTOR
 SHALL BE VENTED. FBC PL 909.1
 PLEASE NOTE, A SEPARATE PERMIT FOR THE GREASE
 INTERCEPTOR IS REQUIRED.
  
 7. PLEASE PROVIDE SIZES AND MINIMUM SLOPES OF PRIMARY
 AND SECONDARY STORM DRAINS. FBC PL 1106.2, TABLE 1106.2
  
 8. PLEASE PROVIDE OVERFLOW SCUPPERS FOR PADEL COURT
 ROOF. FBC PL 1108.1
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH