Plan Review Notes For Permit 22121052 |
Permit Number |
22121052 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-17 13:43:40 | 1ST REVIEW FMC | | PERMIT: 22121052!0 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M6.1: THE RTU-2 AND RTU-3 DO NOT SHOW ANY | | OUTDOOR AIR IN THE EQUIPMENT SCHEDULE. PLEASE SHOW THE | | REQUIRED OUTDOOR AIR FOR EACH RTU AND PROVIDE THE | | OUTDOOR AIR CALCULATION FOR EACH BASED ON THE OCCUPANCY | | CLASSIFICATION. FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | 2) SHEET M2.1: IT APPEARS THE RTU-3 IS RECEIVING RETURN | | AIR FROM A STORAGE ROOM BY THE OFFICE. IF THIS IS A | | RETURN PLEASE REMOVE THIS RETURN DUCT FROM THE CLOSET. | | FMC 601.5 7 | | | | 3) SHOW THAT EACH RTU WILL MEET THE SMOKE DETECTOR | | REQUIREMENTS OF FMC 606.2.1 AND 606.2.2 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|