| 22121052 2025 N DIXIE HWY |
| |
| GAS COMMENTS: DENIED |
| |
| 1. STEEL PIPING BETWEEN METER/REGULATOR AND THE WATER |
| HEATER APPEARS TO TRAVEL UNDERGROUND. PER FBC FG |
| 404.11, PROVIDE METHOD TO PROTECT UNDERGROUND PIPING |
| FROM CORROSION COMPLYING WITH FBC FG 404.11.1, |
| 404.11.2. IF PIPING IS TO BE ROUTED ABOVE GROUND, |
| PLEASE CLARIFY AND INDICATE ON THE PLAN. |
| |
| 2. PLEASE NOTE ON THE PLAN THAT A REGULATOR REDUCING |
| PRESSURE FROM 2 PSI TO THE PRESSURE REQUIREMENTS OF THE |
| WATER HEATER SHALL BE PROVIDED. FBC FG 410.1 |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |