2023-01-11 09:28:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22121052 2025 N DIXIE HWY
  
 GAS COMMENTS: DENIED
  
 1. STEEL PIPING BETWEEN METER/REGULATOR AND THE WATER
 HEATER APPEARS TO TRAVEL UNDERGROUND. PER FBC FG
 404.11, PROVIDE METHOD TO PROTECT UNDERGROUND PIPING
 FROM CORROSION COMPLYING WITH FBC FG 404.11.1,
 404.11.2. IF PIPING IS TO BE ROUTED ABOVE GROUND,
 PLEASE CLARIFY AND INDICATE ON THE PLAN.
  
 2. PLEASE NOTE ON THE PLAN THAT A REGULATOR REDUCING
 PRESSURE FROM 2 PSI TO THE PRESSURE REQUIREMENTS OF THE
 WATER HEATER SHALL BE PROVIDED. FBC FG 410.1
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  