2023-01-25 15:20:05COMMERCIAL ADDITION/REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 2) PLEASE SHOW THE SOUTH WALL OF THE BUILDING WHICH IS
 7 1/2 FEET FROM THE CENTER OF THE ALLY TO BE 1 HOUR
 FIRE RATED PER FBC TABLE 602
  
 3) PLEASE SHOW THE WINDOW AREA ON THE SOUTH WALL OF THE
 BUILDING THAT IS WITHIN THE WALL AREA THAT IS 7 1/2
 FEET FROM THE CENTER OF THE ALLY TO BE 10 PERCENT OR
 LESS OF THAT TOTAL WALL SPACE FBC TABLE 705.8
  
 4) PLEASE SHOW THE WALLS SURROUNDING THE MOP SINK TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 5) PLEASE PROVIDE ROOF TOP MECHANICAL SCREENING DETAILS
 - FBC 1609.1
  
 6) PLEASE PROVIDE DETAILS OR PRODUCT APPROVALS SHOWING
 ATTACHMENTS ETC. FOR THE EXTERIOR CORRIGATED METAL WALL
 FINISH - FBC 1609.1
  
 7) DRAWING S1 SHOWS WIND DESIGN SPEED AS 169MPH - WIND
 SPEED SHOULD BE 170MPH FOR A RISK CATEGORY II BUILDING
 PER FBC WPB SECTION 120
  
 8) PLEASE SHOW THE ROOF TOP OVER FLOW SCUPPERS FOR THE
 HIGHER ROOF - FBC 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS.
  
 9) DRAWING A2.0 DETAIL 2 - PLEASE SHOW THE SHOWER GRAB
 BAR LOCATIONS PER FBC A 608.3.2
  
 10) ACCESSIBLE SHOWER - PLEASE PROVIDE A SHOWER SEAT
 DETAIL PER FBC A 610
  
 11) PLEASE SHOW THE OUTDOOR SERVING COUNTER TO BE
 ACCESSIBLE PER FBC A 904.4 OR 902.3
  
 12) PLEASE SHOW THE STORM WATER DRAINAGE FLOW AWAY FROM
 THE BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE
 SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC
 WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 13) A SEPARATE PERMIT IS REQUIRED FOR - SITE WALL,
 PARKING LOT, FENCES
  
 14) SIDING DETAILS, WINDOW,DOOR AND ROOFING SYSTEM
 PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 FBC WPB 107.3.4.1