2023-02-08 12:41:34 | 3RD GAS REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. DONE |
| |
| 2. DONE |
| |
| 3. THE EXISTANCE OF A HOOD DOES NOT SUPPLY COMBUSTION |
| AIR - YOU NEED TO SHOW THAT THE CALCULATIONS OF THE |
| CUBIC FEET OF THE SPACE USED AND THAT THERE IS AT LEAST |
| 50 CUBIC FEET PER 1000 BTU, OR SUPPLY COMBSTION AIR BY |
| ONE OF THE APPROVED METHODS. YOU SHOULD BE SHOWING ME |
| THE CUBIC FOOT IN A COMMUNICATED SPACE WITHOUT BARRIERS |
| OR DOORS AND DIVIDE BY THE NUMBER OF BTU'S USED. SEE |
| SECTION 304.1 FOR MORE INFORMATION. |
| |
| COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE |
| 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED. |
| - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND |
| CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS |
| NOT NEEDED. |
| |
| 4. DONE |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |