Plan Review Notes
Plan Review Notes For Permit 22121040
Permit Number 22121040
Review Stop G
Sequence Number 3
Notes
Date Text
2023-02-08 12:41:343RD GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. THE EXISTANCE OF A HOOD DOES NOT SUPPLY COMBUSTION
 AIR - YOU NEED TO SHOW THAT THE CALCULATIONS OF THE
 CUBIC FEET OF THE SPACE USED AND THAT THERE IS AT LEAST
 50 CUBIC FEET PER 1000 BTU, OR SUPPLY COMBSTION AIR BY
 ONE OF THE APPROVED METHODS. YOU SHOULD BE SHOWING ME
 THE CUBIC FOOT IN A COMMUNICATED SPACE WITHOUT BARRIERS
 OR DOORS AND DIVIDE BY THE NUMBER OF BTU'S USED. SEE
 SECTION 304.1 FOR MORE INFORMATION.
  
 COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE
 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED.
 - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND
 CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS
 NOT NEEDED.
  
 4. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved