Plan Review Notes For Permit 22121040 |
Permit Number |
22121040 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-02-06 06:28:52 | 2 GAS REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. DONE | | | | 2. DONE | | | | 3. COMBUSTION AIR CALCULATIONS ARE REQUIRED - SHOW THE | | 715,000 BTU HAS ENOUGH AIR WITHIN THE SPACE USED. | | - 2020 FGC 304.1 - - PROVIDE MEASUREMENTS AND | | CALCULATIONS FOR THE COMBUSTION AIR, OR SHOW THAT IT IS | | NOT NEEDED. | | | | 4. DONE | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | |
|