2023-01-06 16:21:161ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22181018
 1/6/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.2: THE REVISED WATER HEATER DETAIL NO.3
 DOES NOT SHOW A MASTER THERMOSTATIC MIXING VALVE WILL
 BE INSTALLED TO LIMIT THE TEMPERATURE OF THE HOT WATER-
 SEC. 607.1.1 FBC P. PLEASE REVISE THE DETAIL TO THE
 SHOW THE DEVICE AND WATER PIPING CONNECTIONS.
  
 2) P3.2: THE REVISED ISOMETRIC SHOWS HOT WATER REMOVED
 FROM THE SINK ON THE ROOF WHICH DOES NOT COMPLY WITH
 SEC. 607.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  