2023-01-05 13:59:09FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE LOAD CALCULATIONS AND ELCTRICAL PANEL
 SCHEDULES FOR ELECTRICAL PANEL 200 AMPS EXISTING
 ELECTRICAL PANEL AND FOR A NEW 100 AMPS SUB-PANEL,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY.
 NEC 215.2, 220, 408.4
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  