2023-02-13 10:59:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA AND IS REQUIRED TO BE LOCATED AT OR ABOVE THE
 ELEVATION OF THE FINISH FLOOR OF THE HABITABLE SPACE OF
 THE DWELLING. FBC R322.1.6
  
 2) THE GENERATOR PAD ENGINEERING DOES NOT MEET THE
 WINDLOAD REQUIREMENTS FOR RISK CATEGORY 1 EXPOSURE D OF
 150 MPH. FBC AMENDMENTS 120.1 THE ENGINEERING FOR THE
 PAD HAS THE R032 GENERAC RATED AT 130 MPH FOR EXPOSURE
 D.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.