Plan Review Notes For Permit 22120925 |
Permit Number |
22120925 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-02-13 10:59:34 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA AND IS REQUIRED TO BE LOCATED AT OR ABOVE THE | | ELEVATION OF THE FINISH FLOOR OF THE HABITABLE SPACE OF | | THE DWELLING. FBC R322.1.6 | | | | 2) THE GENERATOR PAD ENGINEERING DOES NOT MEET THE | | WINDLOAD REQUIREMENTS FOR RISK CATEGORY 1 EXPOSURE D OF | | 150 MPH. FBC AMENDMENTS 120.1 THE ENGINEERING FOR THE | | PAD HAS THE R032 GENERAC RATED AT 130 MPH FOR EXPOSURE | | D. | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|