Plan Review Notes For Permit 22120924 |
Permit Number |
22120924 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-01-09 08:34:12 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING 2ND REVIEW DENIED: | | | | FBC - R 301.2.1.2 SUBMIT AN INSTALLATION SCHEDULE AND | | KEY PLAN FOR THE STORM PANELS. SPECIFY THE OPENING | | SIZE, THE WIND PRESSURES, TYPE OF ANCHOR, ANCHOR | | SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL SPAN, | | SEPARATION DISTANCE FROM PANEL TO GLASS AND THE | | APPLICABLE SECTION NUMBER FROM THE INSTALLATION | | DRAWINGS. FOR YOUR CONVENIENCE I HAVE INCLUDED AN | | INSTALLATION SCHEDULE WITHIN YOUR DIGITAL PORTAL THAT | | HAS MAY BE USED. |
|