Plan Review Notes
Plan Review Notes For Permit 22120894
Permit Number 22120894
Review Stop Z
Sequence Number 2
Notes
Date Text
2023-04-18 13:56:44FAILED
  
 1) THE COLD WATER PIPING IS SHOWN BEING INSTALLED
 DIRECTLY UNDER THE REQUIRED TERMINAL ISLAND OAK TREE
 NORTH OF THE CHILLER ENCLOSURE. WHILE THE PIPE IS
 CALLED OUT AS AT LEAST 36 INCHES BELOW GROUND, THERE
 WOULD BE NO WAY TO MAINTAIN THE SECTION OF PIPE UNDER
 THE TREE WITHOUT REMOVING THE TREE. THE PIPE MUST BE
 INSTALLED AT AN ALTERNATIVE ROUTE AT THIS LOCATION.
  