Plan Review Notes
Plan Review Notes For Permit 22120880
Permit Number 22120880
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-01-11 14:37:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 600 - THERE ARE INDICATIONS OF UNDERGROUND
 FIRE LINES.
  
 UNDERGROUND FIRE LINE WORK SAHLL BE SUBMITTED UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS IN COMPLIANCE WITH
 NFPA 24 AND MANUFACTURE SPECIFICATIONS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
  
 2) SHEET LS 102 - THERE ARE INDICATIONS OF EXIT SIGNAGE
 IN THE MIDDLE OF CORRIDORS/EXIT ACCESS ROUTES/GARAGE
 ACCESS ROUTES THAT ARE SIDE MOUNTS ARE ARE NO VISABLE
 FROM THE ENDS/CORNERS.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.10.1.9 MOUNTING LOCATION. THE BOTTOM OF NEW EGRESS
 MARKINGS
 SHALL BE LOCATED AT A VERTICAL DISTANCE OF NOT MORE
 THAN 6 FT 8 IN.
 (2030 MM) ABOVE THE TOP EDGE OF THE EGRESS OPENING
 INTENDED FOR DES IGNATION BY THAT MARKING. EGRESS
 MARKINGS SHALL BE LOCATED AT A HORI ZONTAL DISTANCE OF
 NOT MORE THAN THE REQUIRED WIDTH OF THE EGRESS OPENING,
 AS MEASURED FROM THE EDGE OF THE EGRESS OPENING
 INTENDED FOR DESIGNA TION BY THAT MARKING TO THE
 NEAREST EDGE OF THE MARKING
  
 7.10.2 DIRECTIONAL SIGNS.
 7.10.2.1 A SIGN COMPLYING WITH 7.10.3, WITH A
 DIRECTIONAL INDICATOR
 SHOWING THE DIRECTION OF TRAVEL, SHALL BE PLACED IN
 EVERY LOCATION WHERE
 THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT IS
 NOT APPARENT.
  
 PLEASE REVIEW AND CORRECT AND COORDINATE WITH THE
 OFFICE OF THE FIRE MARSHAL VIA EMAIL PDF'S OR ZOOM FOR
 REVIEW.
  
  
  
 3) SHEET LS 102 THRU 105 - THERE IS AN INDICATIONS OF A
 DOUBLE SWINGDOOR IN THE CENTER CORRIDOR WITH NO EXIT
 SIGNAGE OVER THE DOOR FROM EACH DIRECTION.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS MARKING, AN EXIT
 SIGN IS REQUIRED OVER THE DOOR IN THE PATH OF EXIT
 TRAVEL.
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 7.10 MARKING OF MEANS OF EGRESS
  
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) SHEET LS 106 - THERE ARE INDICATIONS OF A SPA DECK
 HOWEVER, THERE ARE NO INDICATIONS OF EXIT SIGNS ALONG
 THE EGRESS TRAVEL PATH AND EXIT LOCATIONS.
  
 PER NFPA 101 CH 7
  
 7.10 MARKING OF MEANS OF EGRESS
  
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) SHEET LS 106 - THERE ARE INDICATIONS ARE 2
 HORIZONTAL EXITS WITH LARGE CAPACITIES WITH A SQ FT / 3
 OCC.
  
 PER NFPA 101 , CH 12 ASSEMBY OCCUPANCIES
  
 12.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING
 WITH 7.2.4 SHALL
 BE PERMITTED.
  
 7.2.4.1.2* HORIZONTAL EXITS SHALL BE PERMITTED TO BE
 SUBSTITUTED FOR OTHER
 EXITS PROVIDED THAT BOTH OF THE FOLLOWING ARE MET,
 UNLESS OTHERWISE
 PERMITTED BY 7.2.4.1.3:
 (1) A MINIMUM OF HALF OF THE NUMBER OF EXITS FROM ANY
 COMPARTMENT
 CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN
 HORIZONTAL
 EXITS
 (2) A MINIMUM OF HALF OF THE EGRESS CAPACITY REQUIRED
 FOR ANY COMPARTMENT
 CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN
 HORIZONTAL EXITS
  
 BEFORE ANY SPACE CAN BE USED AS AN OCCUPANT
 ACCUMULATION AREA ON
 EITHER SIDE OF A HORIZONTAL EXIT, IT MUST SATISFY
 CERTAIN CRITERIA. SUCH A
 SPACE, ALTHOUGH SEPARATED WITH 2-HOUR FIRE BARRIERS
 CANNOT BE USED
 AS A HORIZONTAL EXIT UNLESS THERE IS AT LEAST ONE
 STANDARD TYPE OF EXIT (NOT
 AN ADDITIONAL HORIZONTAL EXIT) LEADING FROM THE SPACE,
 TO ENSURE OCCUPANTS
 ARE NOT TRAPPED WITHIN A FIRE COMPARTMENT WITH NO OTHER
 WAY OUT.
 ADDITIONALLY, THE COMPARTMENT MUST BE LARGE ENOUGH TO
 PROVIDE OCCUPANT
 ACCUMULATION SPACE FOR THE OCCU PANTS OF BOTH THE FIRE
 COMPARTMENT
 CONTAINING THE FIRE AND THE NON-FIRE COMPARTMENT,
 ALLOWING 3 SQ FT(0.28 M2
 ) OF FLOOR SPACE PER PERSON.
  
 THERE APPEARS TO BE A CREATION OF EXIT STAGING TYPE
 ROOMS, NOT A SEPARATION OF AN AREA DIVIDED. THERE
 REMAINS THE ABILITY TO WALK AROUND THE EXIT STAGING
 ROOM DEFEATING THE PURPOSE OF A PROPOSED HORIZONTAL
 EXIT.
  
 THERE DOES NOT APPEAR TO BE SUFFICIENT "FLOOR SPACE",
 IN ADDITION TO THE PROPOSED NUMBER OF EXITS AND THEIR
 LOCATIONS.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND CALCULATIONS IN
 COMPLIANCE WITH THE REQUIREMENTS.
  
  
 6) SHEET LS 107 - THERE ARE INDICATIONS ARE A
 HORIZONTAL EXIT WITH A LARGE CAPACITY WITH A SQ FT / 3
 OCC.
  
 PER NFPA 101 , CH 12 ASSEMBY OCCUPANCIES
  
 12.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING
 WITH 7.2.4 SHALL
 BE PERMITTED.
  
 7.2.4.1.2* HORIZONTAL EXITS SHALL BE PERMITTED TO BE
 SUBSTITUTED FOR OTHER
 EXITS PROVIDED THAT BOTH OF THE FOLLOWING ARE MET,
 UNLESS OTHERWISE
 PERMITTED BY 7.2.4.1.3:
 (1) A MINIMUM OF HALF OF THE NUMBER OF EXITS FROM ANY
 COMPARTMENT
 CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN
 HORIZONTAL
 EXITS
 (2) A MINIMUM OF HALF OF THE EGRESS CAPACITY REQUIRED
 FOR ANY COMPARTMENT
 CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN
 HORIZONTAL EXITS
  
 BEFORE ANY SPACE CAN BE USED AS AN OCCUPANT
 ACCUMULATION AREA ON
 EITHER SIDE OF A HORIZONTAL EXIT, IT MUST SATISFY
 CERTAIN CRITERIA. SUCH A
 SPACE, ALTHOUGH SEPARATED WITH 2-HOUR FIRE BARRIERS
 CANNOT BE USED
 AS A HORIZONTAL EXIT UNLESS THERE IS AT LEAST ONE
 STANDARD TYPE OF EXIT (NOT
 AN ADDITIONAL HORIZONTAL EXIT) LEADING FROM THE SPACE,
 TO ENSURE OCCUPANTS
 ARE NOT TRAPPED WITHIN A FIRE COMPARTMENT WITH NO OTHER
 WAY OUT.
 ADDITIONALLY, THE COMPARTMENT MUST BE LARGE ENOUGH TO
 PROVIDE OCCUPANT
 ACCUMULATION SPACE FOR THE OCCU PANTS OF BOTH THE FIRE
 COMPARTMENT
 CONTAINING THE FIRE AND THE NON-FIRE COMPARTMENT,
 ALLOWING 3 SQ FT(0.28 M2
 ) OF FLOOR SPACE PER PERSON.
  
 THERE APPEARS TO BE A CREATION OF AN EXIT STAGING TYPE
 ROOM, NOT A SEPARATION OF AN AREA DIVIDED. THERE
 REMAINS THE ABILITY TO WALK AROUND THE EXIT STAGING
 ROOM DEFEATING THE PURPOSE OF A PROPOSED HORIZONTAL
 EXIT.
  
 THERE DOES NOT APPEAR TO BE SUFFICIENT "FLOOR SPACE",
 IN ADDITION TO THE PROPOSED NUMBER OF EXITS AND THEIR
 LOCATIONS.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND CALCULATIONS IN
 COMPLIANCE WITH THE REQUIREMENTS.
  
  
  
 7) SHEET LS 108, 109, 110 & 111 - THERE ARE INDICATIONS
 ON THE EAST BLDG OF TWO EXIT STAIRWELLS THAT APPEAR TO
 BE SEPARATED BY MORE THAN 200'
  
 NFPA 14 REQUIRES THAT THE DISTANCE OF TRAVEL FROM AN
 OUTLET BE NO MORE THAN 130 FEET IN NON-SPRINKLERED
 BUILDINGS AND NO MORE THAN 200 FEET IN SPRINKLERED
 BUILDINGS.
  
 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A
 NONSPRINKLERED
 FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M)
 OF TRAVEL
 DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A
 REQUIRED
 EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR
 OR STORY
 IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL
 DISTANCE FROM A
 HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT,
 ADDITIONAL
 HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED
 LOCATIONS,
 WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ.
  
 PLEASE REVIEW, CORRECT OR PROVIDE DISTANCE DIMENSIONS
 IN COMPLIANCE WITHE THE REQUIREMENT.
  
  
  
 8) SHEET FP 601 - THERE APPEARS TO BE AN INDICATION OF
 AN ELECTRIC FIRE PUMP.
  
 NFPA 20
  
 9.3 ALTERNATE POWER.
 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT
 LEAST
 ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE
 THE
 HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY
 OF THE
 FIRE DEPARTMENT APPARATUS
 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT
 DESCRIBED IN
 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE
 PROVIDED
 WHERE THE NORMAL SOURCE IS NOT RELIABLE.
  
 9.3.4 WHERE PROVIDED, THE ALTERNATE SOURCE OF POWER
 SHALL BE
 SUPPLIED FROM ONE OF THE FOLLOWING SOURCES:
 (1) A GENERATOR INSTALLED IN ACCORDANCE WITH SECTION
 9.6
 (2) ONE OF THE SOURCES IDENTIFIED IN 9.2.2(1),
 9.2.2(2), 9.2.2(3),
 OR 9.2.2(5) WHERE THE POWER IS PROVIDED INDEPENDENT OF
 THE
 NORMAL SOURCE OF POWER
  
 NFPA 70
  
 ARTICLE 695
 FIRE PUMPS
  
 (D) ON-SITE STANDBY GENERATOR AS ALTERNATE SOURCE. AN
 ON-SITE STANDBY GENERATOR(S) USED AS AN ALTERNATE
 SOURCE OF
 POWER SHALL COMPLY WITH (D)(1) THROUGH (D)(3).
 [20:9.6.2.1]
 (1) CAPACITY. THE GENERATOR SHALL HAVE SUFFICIENT
 CAPACITY
 TO ALLOW NORMAL STARTING AND RUNNING OF THE MOTOR(S)
 DRIV ING THE FIRE PUMP(S) WHILE SUPPLYING ALL OTHER
 SIMULTA NEOUSLY OPERATED LOAD(S). [20:9.6.1.1]
 AUTOMATIC SHEDDING OF ONE OR MORE OPTIONAL STANDBY
 LOADS IN ORDER TO COMPLY WITH THIS CAPACITY REQUIREMENT
 SHALL BE PERMITTED.
  
 FOR CLARIFICATION PURPOSES, PER NFPA 20 & 70 PLEASE
 PROVIDE THE SECONDARY POWER SUPPLY FOR THE ELECTRIC
 FIRE PUMP AND THE FUEL SOURCE OF THE SECONDARY POWER
 SUPPLY.
  
  
  
 9) LIFE SAFETY SHEETS - THERE DOES NOT APPEAR TO BE
 DESIGNATED AREAS OF REFUGE AND THE APPLICABLE
 INDICATORS/EQUIPMENT.
  
 PER NFPA 101 CH 30 NEW APARTMENT OCCUPANCIES
  
 30.2.2.12 AREAS OF REFUGE.
 30.2.2.12.1 AREAS OF REFUGE COMPLYING WITH 7.2.12 SHALL
 BE PERMITTED,
 AS MODIFIED BY 30.2.2.12.2.
 30.2.2.12.2* IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPER VISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 30.3.5, THE TWO
 ACCESSIBLE ROOMS OR SPACES SEPARATED FROM EACH OTHER BY
 SMOKE-RESISTIVE PARTITIONS IN ACCORDANCE WITH THE
 DEFINITION OF AREA OF REFUGE IN 3.3.23
 SHALL NOT BE REQUIRED
  
 NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.12.1 GENERAL.
 7.2.12.1.1 AN AREA OF REFUGE USED AS PART OF A REQUIRED
 ACCESSIBLE MEANS
 OF EGRESS IN ACCORDANCE WITH 7.5.4; CONSISTING OF A
 STORY IN A BUILDING
 THAT IS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRIN KLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7; AND HAVING AN ACCESSIBLE
 STORY THAT IS ONE OR MORE STORIES ABOVE OR BELOW A
 STORY OF EXIT DISCHARGE
 SHALL MEET THE FOLLOWING CRITERIA:
 (1) EACH ELEVATOR LANDING SHALL BE PROVIDED WITH A
 TWO-WAY COMMU NICATION SYSTEM FOR COMMUNICATION BETWEEN
 THE ELEVATOR LANDING
 AND THE FIRE COMMAND CENTER OR A CENTRAL CONTROL POINT
 APPROVED
 BY THE AUTHORITY HAVING JURISDICTION.
 (2) DIRECTIONS FOR THE USE OF THE TWO-WAY COMMUNICATION
 SYSTEM,
 INSTRUCTIONS FOR SUMMONING ASSISTANCE VIA THE TWO-WAY
 COMMUNI CATION SYSTEM, AND WRITTEN IDENTIFICATION OF
 THE LOCATION SHALL BE
 POSTED ADJACENT TO THE TWO-WAY COMMUNICATION SYSTEM.
 (3) THE TWO-WAY COMMUNICATION SYSTEM SHALL INCLUDE BOTH
 AUDIBLE
 AND VISIBLE SIGNALS
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS
 AND CODE REFERENCES FOR NOT PROVIDING THEM.
  
  
 10) RENTAL ELEVATOR PRIVATE LOBBY - THERE DOES NOT
 APPEAR TO BE EXIT SIGNAGE OVER THE EXIT DOOR OF THE
 LOBBY.
  
 PER NFPA 101 CH 30 & 7 EXIT ACCESS SHALL PROVIDE
 MARKINGS OVER EXIT DOORS.
  
 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS
 REQUIRING MORE
 THAN ONE EXIT
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS
 AND CODE REFERENCES FOR NOT PROVIDING THEM.
  
  
 11) EAST FLOOR PLANS - THERE ARE INDICATIONS OF EXIT
 TRAVEL DISTANCES OF THE LARGER UNITS THAT APPEAR TO
 EXCEED THE MAX TRAVEL DISTANCE.
  
 THE BLUE LINE INDICATORS SHOW A STARTING POINT IN AN
 AREA THAT WOULD BE SHORTER THAN AN AREA ON THE SAME
 BALCONY THAT APPEARS TO BE LONGER AND EXCEEDING THE MAX
 TRAVEL DISTANCE OF 125'
  
 PER NFPA 101 CH 30
  
 30.2.6 TRAVEL DISTANCE TO EXITS. TRAVEL DISTANCE SHALL
 BE MEASURED IN
 ACCORDANCE WITH SECTION 7.6
  
 30.2.6.2 TRAVEL DISTANCE WITHIN A DWELLING UNIT
 (APARTMENT) TO A CORRIDOR
 DOOR SHALL NOT EXCEED 125 FT (38 M) IN BUILDINGS
 PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN
 ACCORDANCE WITH 30.3.5
  
 7.6.1* THE TRAVEL DISTANCE TO AN EXIT SHALL BE MEASURED
 ON THE FLOOR OR
 OTHER WALKING SURFACE AS FOLLOWS:
 (1) ALONG THE CENTERLINE OF THE NATURAL PATH OF TRAVEL,
 STARTING FROM THE
 MOST REMOTE POINT SUBJECT TO OCCUPANCY
 (2) CURVING AROUND ANY CORNERS OR OBSTRUCTIONS, WITH A
 12 IN. (305 MM)
 CLEARANCE THEREFROM
 (3) TERMINATING AT ONE OF THE FOLLOWING:
 (A) CENTER OF THE DOORWAY
 (B) OTHER POINT AT WHICH THE EXIT BEGINS
 (C) SMOKE BARRIER IN AN EXISTING DETENTION AND
 CORRECTIONAL OCCU PANCY AS PROVIDED IN CHAPTER 23.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS
 AND CODE REFERENCES FOR NOT PROVIDING THEM.
  
  
 12) SHEET M 101 A, 102 A, 103 A, 104 A, 106 A, 107 A,
 109 A, 110 A B , 111 A B, 112 A B, 113 A B- THERE
 APPEARS TO BE INDICATIONS OF VENTILATION SHAFTS
 BREACHING FIRE RATED WALLS/CORRIDORS THAT DO NOT
 INDICATE FIRE/SMOKE DAMPERS
  
 (SHEET 105 A INDICIATES A F/SD AT THE CENTER CORRIDOR
 UNIT BUT NOT THE OTHER FLOORS NOTED.)
  
 PER NFPA 101 AND 90 A
  
 8.3.5.7 OPENINGS FOR AIR-HANDLING DUCTWORK. OPENINGS IN
 FIRE BARRIERS FOR AIR-HANDLING DUCTWORK OR AIR MOVEMENT
 SHALL
 BE PROTECTED IN ACCORDANCE WITH 9.2.1
  
 8.4.6 AIR-TRANSFER OPENINGS.
 8.4.6.1 GENERAL. THE PROVISIONS OF 8.4.6 SHALL GOVERN
 THE MATERIALS
 AND METHODS OF CONSTRUCTION USED TO PROTECT AIR
 TRANSFER OPENINGS IN SMOKE PARTITIONS.
  
 8.5.5 DUCTS AND AIR-TRANSFER OPENINGS.
 8.5.5.1 GENERAL. THE PROVISIONS OF 8.5.5 SHALL GOVERN
 THE MA TERIALS AND METHODS OF CONSTRUCTION USED TO
 PROTECT DUCTS AND
 AIR-TRANSFER OPENINGS IN SMOKE BARRIERS.
  
 8.5.5.4 INSTALLATION, TESTING, AND MAINTENANCE.
 8.5.5.4.1 AIR-CONDITIONING, HEATING, VENTILATING
 DUCTWORK,
 AND RELATED EQUIPMENT, INCLUDING SMOKE DAMPERS AND
 COMBI NATION FIRE AND SMOKE DAMPERS, SHALL BE INSTALLED
 IN ACCOR DANCE
 WITH NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR
 CONDITIONING AND VENTILATING SYSTEMS, NFPA 90B,
 STANDARD FOR THE
 INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING
 SYSTEMS, NFPA 105, STANDARD FOR SMOKE DOOR ASSEMBLIES
 AND OTHER OPENING
 PROTECTIVES, OR NFPA 80, STANDARD FOR FIRE DOORS AND
 OTHER OPENING PROTECTIVES, AS APPLICABLE
  
 PLEASE REVIEW AND CORRECT OR PROVIDE CLARIFICATIONS
 WITH SPECIFIC JUSTIFICATION INCLUDING CODE REFERENCES.
  
  
 13) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 14) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  