Plan Review Notes
Plan Review Notes For Permit 22120859
Permit Number 22120859
Review Stop SIGNATURE
Sequence Number 3
Notes
Date Text
2023-02-27 08:37:021) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR EACH UNIT. FEC C403.2.1 AND FMC 312.1
 2) THE ELECTRONIC SIGNATURES ON THE DRAWINGS ARE COPIES
 OF THE ORIGINAL. DIGITALLY SUBMIT THE ORIGINAL
 DIGITALLY SIGNED DRAWINGS INTO THE PROJECT???S PORTAL.
 FS 471/481