Plan Review Notes
Plan Review Notes For Permit 22120859
Permit Number 22120859
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-01 14:59:05ELECTRIC REVIEW FAILED
 APPLICATION STATES 4 MINI SPLIT SYSTEMS. PLANS DETAIL 2
 APARTMENT UNITS WITH COMPLETE ELECTRIC SYSTEM
 .
 PLEASE PROVIDE ELECTRICAL FLOOR PLANS WITH ONLY THE
 ELECTRIC WORK PERFORMED UNDER THIS SUBMITTAL.
 INDICATE ON PLANS CONDENSING AND ASSOCIATED INDOOR
 UNITS BY APARTMENT NUMBERS. PROVIDE PLANS FOR ALL 4
 APARTMENT UNITS. INCLUDE ALL CONDUIT, CONDUCTOR,
 OVERCURRENT PROTECTION SIZES AND WIRING METHODS USED.
  
 FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER