Plan Review Notes For Permit 22120852 |
Permit Number |
22120852 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-30 13:34:29 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) | | RELEASE OF SERVICE CONFIRMATION. | | PLEASE PROVIDE ELECTRIC PERMIT INFORMATION FOR THE | | REMOVAL OF POWER POLES AND SAFE DISCONNECTING OF | | ELECTRIC. | | | | 3. WATERDOWN METHOD: | | SINCE A BACKFLOW PREVENTER DEVICE HAS BEEN SELECTED AS | | THE METHOD OF WATERING DOWN SITE DURING DEMOLITION, | | PLEASE INFORM ME WHEN THE PLUMBING FINAL INSPECTION | | #703 HAS BEEN APPROVED. BEFORE SCHEDULING THE #703 | | PLUMBING FINAL INSPECTION, THE BACKFLOW DEVICE NEEDS TO | | BE TESTED AND CERTIFIED BY THE CITY PUBLIC UTILITIES | | DEPARTMENT, 561 822 2244. FAX THE COMPLETED "DEMOLITION | | APPLICATION" FORM TO | | 561-822-2183. | | | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | APPLICATION TO BUILDING DIVISION); | | SCHEDULE A FINAL PLUMBING #703 INSPECTION AND INFORM ME | | WHEN THE PLUMBING FINAL INSPECTION #703 HAS BEEN | | APPROVED. | | |
|