Plan Review Notes
Plan Review Notes For Permit 22120760
Permit Number 22120760
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-26 09:43:491ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. ISOMETRIC - UPSTAIRS BATH #4 - 2020 FRC P3108.2.1 -
 WATER CLOSET AND SHOWER ARE NOT VENTED TO CODE. ONLY
 ONE FIXTURE IS ALLOWED UPSTREAM OF THE VENTED FIXTURE'S
 CONNECTION TO THE HORIZONTAL BRANCH. RECONFIGURE
 BATHROOM.
  
 2. ISOMETRIC - UPSTAIRS BATH #3 - 2017 WPB AMEND
 107.3.5.3 (12) - THE TUB SEEMS TO BE MISSING FROM THE
 ISOMETRIC.
  
 3. ISOMETRIC - DOWNSTAIRS BATH #2 - 2020 FRC P3108.2.1
 - WATER CLOSET AND SHOWER ARE NOT VENTED TO CODE. ONLY
 ONE FIXTURE IS ALLOWED UPSTREAM OF THE VENTED FIXTURE'S
 CONNECTION TO THE HORIZONTAL BRANCH. RECONFIGURE
 BATHROOM.
  
 4. ISOMETRIC - DOWNSTAIRS LAUNDRY ROOM - SECTION FRC
 P3112 - THE VENT FOR THE WASHING MACHINE IS
 INACCURATELY LABELED AS A LOOP VENT. BRANCH VENT IS
 MORE ACCURATE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved