2023-02-02 15:47:45FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW LOAD CALCULATION (AC UNITS). NEC 220.82
 2. PROVIDE CORRECT EQUIPMENT GROUNDING CONDUCTOR (EGC)
 FOR POOL PANEL 60A POWERED FROM THE 'B' PANEL 150A. NEC
 TABLE 250.122
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  