2023-01-12 17:01:151ST REVIEW FMC
 PERMIT: 22120724
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL SIZING CALCULATIONS ARE REQUIRING A
 5- TON UNIT, THE A/C EQUIPMENT SCHEDULE IS ALSO CALLING
 FOR A 5-TON UNIT BUT THE MECHANICAL DRAWING IS SHOWING
 A 4- TON SYSTEM IN THE ATTIC. PLEASE MAKE SURE THE
 MECHANICAL SYSTEM IS CONSISTENT ON BOTH DOCUMENTS. FBC
 107.3.5
  
 2) PROVIDE THE DUCT SIZES ON ALL DUCTWORK INCLUDING THE
 SUPPLY AND RETURN DUCTS AT THE MECHANICAL UNIT. FBC
 107.3.5
  
 3) THE RANGE HOOD MUST MEET THE REQUIREMENTS OF FRC
 M1503.4
  
 4) SHOW THE DRYER EXHAUST DUCT SIZE AND TERMINATION
 LOCATION ON THE DRAWING. FRC M1502
  
 5) SHOW THE CONDENSATE DRAIN PIPE SIZE AND TERMINATION
 LOCATION ON THE DRAWING. FRC M1411.3
  
 6) SHOW THE BATH EXHAUST FAN, DUCT AND TERMINATION
 LOCATION ON THE DRAWING FOR THE BATHROOM NEAR THE
 WASHER AND DRYER. FRC R303.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  