Plan Review Notes
Plan Review Notes For Permit 22120711
Permit Number 22120711
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-16 07:58:101ST REVIEW FBC-2020 PLUMBING
 PERMIT-22120711
 12/16/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT A MANUFACTURER???S SPEC SHEET FOR THE
 BACKFLOW PREVENTER THAT INDICATES THE MAKE AND MODEL OF
 THE DEVICE AND THAT IT IS LEAD-FREE AND ON THE APPROVED
 DEVICE LIST PUBLISHED BY THE UNIVERSITY OF SOUTHERN
 CALIFORNIA- WPB UTILITIES CROSS-CONNECTION MANUAL.
 PLEASE NOTE A REDUCED PRESSURE PRINCIPLE BACKFLOW
 PREVENTER IS REQUIRED FOR POTABLE WATER SERVICES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  