2023-01-25 09:54:23BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22120625
 412 CLEMATIS ST
  
 1- SIGN MEANS OF ATTACHMENT WAS REVISED. GENERAL
 STATEMENT DESCRIBED IN THE REVISED SIGN MEANS OF
 ATTACHMENT IS NOT ACCEPTABLE. ENGINEER OF RECORD NEEDS
 TO SPECIFY THE ANCHOR TYPE, SIZE AND SPACING AND NUMBER
 OF FASTENERS. SEC. 1609.1 FBC-BUILDING.
  
 2- ENGINEER NEEDS TO PROVIDE COMPLETE DESIGN CRITERIA
 INCLUDING THE CURRENT BUILDING CODE, ULTIMATE DESIGN
 WIND SPEED AND NOMINAL DESIGN WIND SPEED, WIND
 EXPOSURE, RISK CATEGORY AND DESIGN WIND PRESSURES AS
 REQUIRED BY SEC. 1603.1.4 FBC-BUILDING. SEC. 107.3.5
 CITY AMENDMENTS.
  
 3- REVISED STRUCTURAL DRAWINGS WERE NOT SIGNED AND
 SEALED. ALL DOCUMENTS PREPARED BY A LICENSED ENGINEER
 NEED TO HAVE THE ORIGINAL VERIFIABLE DIGITAL SIGNATURE
 OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.004 FAC AND CHAPTER 471 F.S.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  