2023-01-13 14:41:49 | BUILDING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #22120625 | | 412 CLEMATIS ST | | | | 1- ENGINEER TO PROVIDE COMPLETE DESIGN CRITERIA | | INCLUDING THE CURRENT BUILDING CODE, ULTIMATE DESIGN | | WIND SPEED AND NOMINAL DESIGN WIND SPEED, WIND | | EXPOSURE, RISK CATEGORY AND DESIGN WIND PRESSURES AS | | REQUIRED BY SEC. 1603.1.4 FBC. SEC. 107.3.5 CITY | | AMENDMENTS. | | | | 2- ENGINEER TO PROVIDE COMPLETE DETAIL/SPECIFICATIONS | | FOR INDIVIDUAL LETTERS ATTACHMENT. SEC. 1609.1 | | FBC-BUILDING. | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|