2022-12-16 10:06:55 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. PROVIDE THE FOLLOWING ADDITIONAL INFORMATION FOR |
| MIAMI-DADE NOA NO.: 18-0919.12 FOR THE PROPOSED FLAT |
| ROOF SYSTEM TO BE USED. LIMITATIONS PAGE #67. SELECT |
| FASTENING OPTION TO BE USED. FASTENING OPTIONS 1, 2, 3 |
| & 4 CANNOT BE USED. GENERAL LIMITATION #9 IS |
| SPECIFICALLY REFERRED TO. THE MAXIMUM DESIGNED PRESSURE |
| LIMITATION LISTED SHALL BE APPLICABLE TO ALL ROOF |
| PRESSURE ZONES (I.E. FIELD, PERIMETERS, AND CORNERS). |
| NEITHER RATIONAL ANALYSIS, NOR EXTRAPOLATION SHALL BE |
| PERMITTED FOR ENHANCED FASTENING AT ENHANCED PRESSURE |
| ZONES (I.E. PERIMETERS, EXTENDED CORNERS AND CORNERS). |
| FASTENING OPTIONS 3 & 5 ENGINEERED SIGNED AND SEALED |
| CALCULATIONS WILL BE REQUIRED AS PER LIMITATIONS #7. |
| ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. THIS |
| PROJECT IS LOCATED IN AN EXPOSURE CATEGORY C AREA. |
| 2. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |