Plan Review Notes For Permit 22120572 |
Permit Number |
22120572 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2023-02-07 14:43:30 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC B 107.2.1 PROVIDE THE FOLLOWING INFORMATION FOR | | MIAMI-DADE COUNTY NOA NO.: 20-0131.07 THE PROPOSED FLAT | | ROOF SYSTEM TO BE USED CORRESPONDING TO THE SUBMITTED | | ENGINEERS CALCULATIONS. COVER PAGES #1-2, INSTALLATION | | INSTRUCTIONS FOR SYSTEM A (1) PAGE #7 AND LIMITATIONS | | PAGE #18. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST | | BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. | | 2. SUBMITTED ENHANCED NAILING CALCULATIONS ARE NOT | | SIGNED AND SEALED. UPLOAD A VALID ELECTRONICALLY SIGNED | | PLAN/DOCUMENT TO PROJECTDOX. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|