Plan Review Notes For Permit 22120572
Permit Number 22120572
Review Stop B
Sequence Number 1
Notes
Date Text
2022-12-15 08:46:42JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 17-0822.08 HAS EXPIRED AND IS NO LONGER VALID. PLEASE
 PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA???S FOR THE PROPOSED ROOF EDGE
 TERMINATION SYSTEM TO BE USED. INCLUDE COVER PAGE,
 EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150.
 SUBMITTED MIAMI-DADE COUNTY NOA 20-0818.03 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A (1) THROUGH F (1).
 SELECT SYSTEM TYPE TO BE USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. GENERAL LIMITATION #7 IS
 SPECIFICALLY REFERRED TO IN THIS NOA. FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT,
 OR REGISTERED ROOF CONSULTANT MAY BE REQUIRED. THIS
 PROJECT IS LOCATED IN AN EXPOSURE CATEGORY C AREA.
 3. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND
 SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT, OR REGISTERED ROOF CONSULTANT.
 4. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF
 DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE
 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020
 FBC-PLUMBING.
 5. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  