2022-12-15 08:46:42 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA |
| 17-0822.08 HAS EXPIRED AND IS NO LONGER VALID. PLEASE |
| PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA???S FOR THE PROPOSED ROOF EDGE |
| TERMINATION SYSTEM TO BE USED. INCLUDE COVER PAGE, |
| EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR |
| SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. |
| 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT |
| LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150. |
| SUBMITTED MIAMI-DADE COUNTY NOA 20-0818.03 COVERS |
| MULTIPLE ROOFING SYSTEMS TYPES A (1) THROUGH F (1). |
| SELECT SYSTEM TYPE TO BE USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. GENERAL LIMITATION #7 IS |
| SPECIFICALLY REFERRED TO IN THIS NOA. FASTENER DENSITY |
| CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA |
| REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, |
| OR REGISTERED ROOF CONSULTANT MAY BE REQUIRED. THIS |
| PROJECT IS LOCATED IN AN EXPOSURE CATEGORY C AREA. |
| 3. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND |
| SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A |
| FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| 4. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF |
| DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE |
| 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020 |
| FBC-PLUMBING. |
| 5. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |