2023-02-24 17:13:12 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22120561 |
| 2/24/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) 2ND REQUEST: SHEET P.100 SHOWS A NEW BACKFLOW |
| PREVENTER AND A GREASE WASTE LINE TO A GREASE |
| INTERCEPTOR. BOTH OF THESE ITEMS REQUIRE SEPARATE |
| PERMITS AND APPLICATION FOR EACH SHALL BE SUBMITTED |
| PRIOR TO APPROVAL OF THE MAIN PLUMBING PLANS. YOU CAN |
| SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO |
| NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED |
| PERMIT APPLICATION TO [email protected]. YOU WILL |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND |
| THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA |
| EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| A) P.100: NUMEROUS REFERENCES TO CIVIL PLANS ARE MADE |
| IN THE PLAN NOTES FOR THE LOCATIONS OF THE WATER METER, |
| GREASE INTERCEPTOR, SANITARY AND STORM DRAINAGE |
| CONNECTIONS TO MAINS ETC. THE CIVIL PLANS ARE REQUIRED |
| FOR ENGINEERING REVIEW HOWEVER THEY WILL NOT DELAY |
| PLUMBING PLAN APPROVAL. PLEASE NOTE THE LOCATION OF THE |
| INTERCEPTOR SHALL BE SHOWN ON THE SEPARATELY PERMITTED |
| PLAN. |
| |
| 2) P.100 GREASE INTERCEPTOR PLAN REVIEW SUBMITTAL |
| REQUIREMENTS: |
| |
| A) EQUIPMENT SCHEDULE INDICATING THE MAKE, MODEL, AND |
| CAPACITY OF THE UNIT. |
| |
| B) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 |
| FOR GRAVITY TYPES. |
| |
| C) PLUMBING PIPING DIAGRAM INCLUDING THE LOCATIONS AND |
| SIZES OF THE INLET AND OUTLET PIPES, CLEANOUTS, VENT |
| PIPES, AND OUTLET PIPE POINT OF CONNECTION TO THE MAIN |
| SANITARY LINE. |
| |
| D) CLEANOUT ASSEMBLY DETAIL INCLUDING THE MAKE AND |
| MODEL AND TYPE OF ACCESS LID TO BE INSTALLED IF LOCATED |
| IN A VEHICLE TRAFFIC AREA. PLEASE NOTE THE WPB |
| UTILITIES DEPT. USES THE CLEANOUT ACCESS FOR PERIODIC |
| GREASE SAMPLING. |
| |
| E) MANUFACTURER'S SPECIFICATIONS FOR THE INTERCEPTOR |
| AND ACCESS LIDS ARE REQUIRED FOR FINAL APPROVAL BUT CAN |
| BE DEFERRED SUBMITTALS AND BE ONSITE FOR INSPECTION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |