2023-02-24 17:13:122ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22120561
 2/24/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST: SHEET P.100 SHOWS A NEW BACKFLOW
 PREVENTER AND A GREASE WASTE LINE TO A GREASE
 INTERCEPTOR. BOTH OF THESE ITEMS REQUIRE SEPARATE
 PERMITS AND APPLICATION FOR EACH SHALL BE SUBMITTED
 PRIOR TO APPROVAL OF THE MAIN PLUMBING PLANS. YOU CAN
 SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 A) P.100: NUMEROUS REFERENCES TO CIVIL PLANS ARE MADE
 IN THE PLAN NOTES FOR THE LOCATIONS OF THE WATER METER,
 GREASE INTERCEPTOR, SANITARY AND STORM DRAINAGE
 CONNECTIONS TO MAINS ETC. THE CIVIL PLANS ARE REQUIRED
 FOR ENGINEERING REVIEW HOWEVER THEY WILL NOT DELAY
 PLUMBING PLAN APPROVAL. PLEASE NOTE THE LOCATION OF THE
 INTERCEPTOR SHALL BE SHOWN ON THE SEPARATELY PERMITTED
 PLAN.
  
 2) P.100 GREASE INTERCEPTOR PLAN REVIEW SUBMITTAL
 REQUIREMENTS:
  
 A) EQUIPMENT SCHEDULE INDICATING THE MAKE, MODEL, AND
 CAPACITY OF THE UNIT.
  
 B) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
  
 C) PLUMBING PIPING DIAGRAM INCLUDING THE LOCATIONS AND
 SIZES OF THE INLET AND OUTLET PIPES, CLEANOUTS, VENT
 PIPES, AND OUTLET PIPE POINT OF CONNECTION TO THE MAIN
 SANITARY LINE.
  
 D) CLEANOUT ASSEMBLY DETAIL INCLUDING THE MAKE AND
 MODEL AND TYPE OF ACCESS LID TO BE INSTALLED IF LOCATED
 IN A VEHICLE TRAFFIC AREA. PLEASE NOTE THE WPB
 UTILITIES DEPT. USES THE CLEANOUT ACCESS FOR PERIODIC
 GREASE SAMPLING.
  
 E) MANUFACTURER'S SPECIFICATIONS FOR THE INTERCEPTOR
 AND ACCESS LIDS ARE REQUIRED FOR FINAL APPROVAL BUT CAN
 BE DEFERRED SUBMITTALS AND BE ONSITE FOR INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  