2023-02-27 15:39:06 | ADJUST THE OUTDOOR AIR CALCULATION FOR THE LOBBY. A | | LOBBY IS 150 OCCUPANTS PER 1000 SQ. FT. X 5 CFM PER | | OCCUPANT + SQ. FT. X .06 FOR SPACE CFM. THE OCCUPANT | | COUNT FOR THIS SPACE IS 25 OCCUPANTS. FMC 403.3.1.1 AND | | TABLE 403.3.1.1 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|