2023-02-27 15:39:06ADJUST THE OUTDOOR AIR CALCULATION FOR THE LOBBY. A
 LOBBY IS 150 OCCUPANTS PER 1000 SQ. FT. X 5 CFM PER
 OCCUPANT + SQ. FT. X .06 FOR SPACE CFM. THE OCCUPANT
 COUNT FOR THIS SPACE IS 25 OCCUPANTS. FMC 403.3.1.1 AND
 TABLE 403.3.1.1
  