2023-02-21 13:46:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22120561 |
| ADD: 915 N. RAILROAD AVE. |
| CONT: HEDRICK BROTHERS CONSTRRUCTION |
| TEL: 561-308-2954 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. FEB. 21ST/2023 |
| ACTION: DENIED |
| |
| 1) SHEET T100 TITLE SHEET: |
| 1A) COMLIED. SHEET S102. |
| |
| 1B) NOTE ONLY. 2020 EXISTING BUILDING CODE. 801.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1C) BUILDING PROVISO: DEFERRED SUBMITTALS: |
| COMPONENTS & CLADDING. |
| (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: CURTAINWALL, STOREFRONTS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE INSULATION, ROOF TOP VENTILATORS |
| (E) PRE-ENGINEERED ROOFTOP A/C STANDS |
| STAIR & ELEVATOR SHOP DRAWINGS |
| ROOF ACCESS LADDER SHOP DRAWINGS |
| FRONT CANOPY SHOP DRAWINGS |
| STEEL SHOP DRAWINGS |
| |
| 1D) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF |
| APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 1E) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. |
| PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND |
| SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| USED IN THE TESTS. |
| |
| |
| 2) REQUIRED BEFORE PERMIT ISSUANCE. SHEET S001 GENERAL |
| NOTES: GEOTECHNICAL INVESTIGATIVE REPORT. PLEASE |
| PROVIDE THE ENGINEERING REPORT LISTED BY UNIVERSAL |
| ENGINEERING SCIENCES, DATED FEB. 07TH, 2022. 2020 |
| FBC-BUILDING 1803.5.2 QUESTIONABLE SOIL. |
| |
| 3) SHEET S002 GENERAL NOTES: |
| 3A) BUILDING PROVISO: WELDING. WELDED OR BOLTED |
| CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND |
| OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| CERTIFICATION WILL BE REQUIRED. |
| THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| INSPECTION. |
| 2020 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| BRUNELLE AT 561-805-6670. |
| |
| 3B) COMPLIED. |
| |
| 4) SHEET A101: |
| 4A) SEMI -COMPLIED. WITH THE CREATION OF 2 VESTIBULES |
| THE LOBBY VESTIBULE HAS A INSWING DOOR THERE IS A EXIT |
| LIGHT SHOWN FROM 1ST FLOOR FUTURE TENANT 105. THIS |
| PROPOSE SPACE IS TO BE A RESTAURANT AND THE OCCUPANT |
| LOAD SHOWN TO GO THROUGH THIS DOOR IS 206. 2020 |
| FBC-BUILDING CODE SECTION 1010.1.2.1. OCCUPANT LOADS 50 |
| OR MORE REQUIRE THE DOOR TO SWING IN THE EXIT TRAVEL. |
| 1ST ROUND OF COMMENTS. THE FLOOR PLAN SHOWS TWO |
| OUTSWING DOORS, IT APPEARS THAT THEY SWING OUT OVER THE |
| PROPERTY LINE AND INTO THE RIGHT-OF-WAY. SEE SECTION |
| 3202.2 2020 FBC-BUILDING CODE. SEE SURVEY IT APPEARS |
| THE PROPERTY LINE IS THE FRONT OF THE BUILDING. |
| |
| 4B) COMPLIED. |
| |
| 5) 2ND REQUEST. THE LIFE SAFETY PLAN DOES NOT PROVIDE |
| WHAT THE EGRESS CAPACITY FACTOR, YOU ARE USING FOR THE |
| STAIRS AND DOORWAYS. SHEET A601 SHOWS THE ENTRY DOOR |
| 102A TO BE 2 FEET 11 ?? INCHES WIDE, THE CLEAR WIDTH |
| WOULD BE 33.5 INCHES. 33.5 INCHES/ 0.2= 167 OCCUPANTS |
| THROUGH THAT DOOR. SEE 1ST ROUND COMMENT. |
| 1ST ROUND OF COMMENTS. SHEET LS101 & LS102 THE 3 FEET |
| WIDE EXIT DOORS ARE TAKING A CLEAR WIDTH OF 35 INCHES |
| OR 178 OCCUPANTS. 2020 ACCESS. CODE 404.2.3. CLEAR |
| WIDTH & SIZE OF DOORS, 2020 FBC-B 1010.1.1. THE MINIMUM |
| SIZE OF A SWING DOORS IS MEASURED CLEAR OPENING OF THE |
| DOORWAY WITH THE SWINGING DOORS SHALL BE MEASURED |
| BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE |
| DOOR OPEN 90 DEGREES. 34INCHES/ 0.20= 170 OCCUPANTS NOT |
| THE 178. PLEASE ADDRESS CLEAR WIDTH OF ALL EGRESS |
| DOORS. |
| |
| |
| |
| 6) 2ND REVIEW. UNRESOLVED. IT IS TRUE YOUR CONCERNS ARE |
| WHAT HAPPENS WITHIN THE PROPERTY LINES, E-MAILS HAVE |
| BEEN SENT TO ENGINEERING TO SEE IF THERE IS FUTURE |
| PLANS IN THE WORKS FOR FURTHER STREET SCAPE WORK. |
| WITH SPEAKING WITH THE CITY SURVEYOR TO DATE ONLY WATER |
| AND SEWER PLANS WERE SUBMITTED NO CIVIL FOR THE NORA |
| PROJECT. |
| SHEET A401 FRONT ELEVATION. THE FRONT ELEVATION SHOWS |
| THE CITY SIDEWALK RAMPED UP TO MEET YOUR NEW FINISH |
| FLOOR LEVEL, IT APPEARS THE CITY SIDEWALK IS RAISED AN |
| ADDITIONAL 6 INCHES AT THE NEW DOORWAYS, PLEASE PROVIDE |
| WHY THIS OCCURS WITH A NEW CONSTRUCTION ON THE EAST AND |
| WEST WALLS? 2020 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. |
| CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 7) SHEET A301: |
| 7A) SEMI-COMPLIED. THE SHEET A301 NOR A302 NOR THE |
| STRUCTURAL SHEETS SHOW THE SIZE OF THE ROOF HATCH NOR |
| THE REQUIRED FRAMING DIMENSIONS REQUIRED FOR THE LAYOUT |
| OF JOIST AND ANY ADDITIONAL FRAMING REQUIRED TO ANCHOR |
| THE ROOF HATCH TOO. |
| |
| 1ST ROUND COMMENTS. THE ROOF PLAN SHOWS THE USE OF A |
| ROOF HATCH AND DETAIL TO GAIN ACCESS ONTO THE ROOF. THE |
| ROOF HATCH SHOWS A CLEAR OPENING OF 3X3=9 SQ. FT. |
| PLEASE REVIEW IN THE 2020 FBC-BUILD CODE SECTION |
| 1011.12.2 ROOF ACCESS THE EXCEPTION, THE ROOF HATCH |
| SHALL NOT BE LESS THAN 16 SQ. FT. IN AREA AND HAVING A |
| MINIMUM DIMENSION OF 2 FEET. 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 7B) 2ND REQUEST. REVISION 1 PROVIDES THE LOCATIONS BUT |
| NOT THE MINIMUM REQUIRED SIZE DEPENDING ON THE ANNUAL |
| RAINFALL AND SIZING ACCORDING TO THE FBC-PLUMBING CODE |
| CHAPTER 11. |
| 1ST ROUND OF COMMENTS. ROOF OVERFLOW SCUPPERS ARE SHOWN |
| DETAIL GIVEN 5/A-303 BUT NEITHER PROVIDE THE MINIMUM |
| WIDTH AND HEIGHT IN ACCORDANCE WITH 1503.4.1 THE SIZING |
| AND INSTALLATION OF THE SECONDARY OVERFLOW IN |
| ACCORDANCE WITH FBC-PLUMBING CODE CHAPTER 11. |
| |
| 8) SHEET A502: |
| 8A) BUILDING PROVISO: BEFORE FLOOR REMOVAL STARTS. |
| SHEET A502. NOTE STATES THE GC SHALL HIRE A LICENSED |
| SHORING ENGINEER TO TEMPORARY SUPPORT THE EXISTING WALL |
| OF 905/ AND 915. SHOW COMPLIANCE WITH BOTH SECTIONS |
| 1803.5.7 & 1804.2.1. THE UNDERPINNING SEQUENCE OF |
| INSTALLATION SHALL BE IDENTIFIED AND INSTALLED IN |
| ACCORDANCE WITH APPROVED CONSTRUCTION DOCUMENTS. 2020 |
| FBC-BUILDING. |
| |
| 8B) 2ND REVIEW. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES "CODE SECTIONS SHALL |
| NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM |
| "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| SPECIFIC INFORMATION". |
| 1ST REVIEW. THE ELEVATOR SECTION SHOWS THE USE OF |
| UNDERGROUND HYDRAULIC ELEVATOR CYLINDER. PLEASE PROVIDE |
| COMPLIANCE WITH THE 2020 FBC-BUILDING CODE SECTION |
| 3011.1.1-3011.1.3. |
| |
| 8C) COMPLIED. NOT APPLICABLE NO MACHINE ROOM. |
| |
| 9) DEFERRED SUBMITTAL: LIQUID APPLIED FLASHING DOORS |
| AND WINDOWS TO BE REVIEWED BY THE DESIGNER OF RECORD |
| BEFORE SUBMITTAL TO THE BUILDING DIVISION. |
| |
| 10) DEFERRED SUBMITTALS A/C STANDS. |
| |
| 11) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT |
| REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |